| 2009-09-09 11:45:55 | BUILDING PLAN REVIEW |
| | PERMIT: 09080604 |
| | ADD: 519 CLEMATIS ST. |
| | CONT: SEC |
| | TEL: (561)797-6007 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | 09-09-09 |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | |
| | 2) PLANS ARE DEFICIENT IN THE FOLLOWING ITEMS, 106.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS: |
| | 106.3.5(2) OCCUPANCY GROUP AND SPECIAL OCCUPANCY |
| | REQUIREMENTS SHALL BE DETERMINED. |
| | |
| | (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | |
| | (4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS TABLE 601 |
| | |
| | (5) FIRE SUPPRESSION SYSTEMS, ARE THER FIRE SPRINKLERS? |
| | 903 |
| | PLANS DO NOT PROVIDE FIRE EXTINGUISHER LOCATIONS 906.1 |
| | |
| | (6) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | |
| | (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD TABLE 1004.1.1 |
| | MEANS OF EGRESS / EXIT ACCESS 1015/ AISLE ACCESSWAYS |
| | 1014.4.3.3 |
| | |
| | (8) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | 803.1/ TABLE 803.5 |
| | SANITATION 1210.2 |
| | |
| | (9) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | ACCESSIBLE ROUTE BOTH FOR THE INTERIOR AND PATIO DECK |
| | RESTROOMS |
| | |
| | 3) SHEET A.02 INDICATESA STALL WITHIN THE MENS |
| | RESTROOM, THE NEW WORK SHEET A.03 INDICATES THE STALL |
| | NOW DOES NOT HAVE A TURNING RADIUS WITHIN THE STALL, |
| | PLEASE REVIEW 11-4.1.6 ACCESSIBLE BUILDINGS- |
| | ALTERATIONS (1) |
| | A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES OR |
| | HAS THE EFFECT OF DECREASING ACCESSIBILITY OR USABILITY |
| | OF A BUILDING OR FACILITY BELOW THE REQUIREMENTS FOR |
| | NEW CONSTRUCTION AT THE TIME OF ALTERATION. |
| | |
| | (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE |
| | ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE, |
| | FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE |
| | PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3, |
| | MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE |
| | APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT |
| | AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE |
| | ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS |
| | NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS |
| | PROVIDED IN SECTION 11-4.1.6(2), ALTERATIONS TO AN AREA |
| | CONTAINING A PRIMARY FUNCTION. |
| | |
| | (C) IF ALTERATIONS OF SINGLE ELEMENTS, WHEN CONSIDERED |
| | TOGETHER, AMOUNT TO AN ALTERATION OF A ROOM OR SPACE IN |
| | A BUILDING OR FACILITY, THE ENTIRE SPACE SHALL BE MADE |
| | ACCESSIBLE. |
| | |
| | 4) PLEASE ALSO PROVIDE A FLOOR PLAN INDICATING |
| | COMPLIANCE WITH : |
| | 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS |
| | SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH |
| | THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35. |
| | WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS |
| | CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT |
| | LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED |
| | TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE |
| | ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS |
| | REQUIRED IN SECTION 11-4.1.3(18). ETWEEN THE SMOKING |
| | AND NONSMOKING AREAS. IN NEW CONSTRUCTION, AND WHERE |
| | PRACTICABLE IN ALTERATIONS, ACCESSIBLE FIXED TABLES (OR |
| | COUNTERS) SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR |
| | FACILITY. |
| | |
| | 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS SERVED |
| | AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN HEIGHT FOR |
| | CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING |
| | AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS |
| | 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE PROVIDED |
| | IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE |
| | AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA. |
| | |
| | 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL |
| | BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36 |
| | INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES |
| | OR BETWEEN A WALL AND THE TABLE EDGES. |
| | |
| | 11-5.4 DINING AREAS. IN NEW CONSTRUCTION, ALL DINING |
| | AREAS, INCLUDING RAISED OR SUNKEN DINING AREAS, |
| | LOGGIAS, AND OUTDOOR SEATING AREAS, SHALL BE |
| | ACCESSIBLE. IN ALTERATIONS, ACCESSIBILITY TO RAISED OR |
| | SUNKEN DINING AREAS, OR TO ALL PARTS OF OUTDOOR SEATING |
| | AREAS IS NOT REQUIRED PROVIDED THAT THE SAME SERVICES |
| | AND DECOR ARE PROVIDED IN AN ACCESSIBLE SPACE USABLE BY |
| | THE GENERAL PUBLIC AND ARE NOT RESTRICTED TO USE BY |
| | PEOPLE WITH DISABILITIES. |
| | |
| | 5) DESIGN LOADS SHEET A.04 & A.05 BOTH INDICATE A |
| | 120MPH / 3SECOND GUST, PLEASE REVIEW FIGURE 1609 THE |
| | CITY OF WEST PALM BEACH IS ENTIRELY LOCATED WITHIN A |
| | 140 MPH WIND ZONE, PLEASE UPDATE PLANS. |
| | |
| | 6) DESIGN LOADS SHEET A.04 & A.05 BOTH INDICATE FLOOR |
| | LOADS OF 40 PSF LIVE LOADS PLEASE REVIEW TABLE 1607.1 |
| | DINING ROOMS & RESTARAUNTS OF 100 PSF, OR ASSEMBLY WITH |
| | MOVABLE SEATS 100 PSF. |
| | PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE OF |
| | FLOOR SYSTEM, PLANS APPEAR TO INDICATE A FLOOR TRUSS |
| | SYTEM? |
| | |
| | 7) BOTH A.05 & S1 BOTH INDICATE A NEW OPENING ON THE |
| | SIDE OF THE BUILDING WITH A PAIR OF GLAZED OPENINGS & |
| | TWO SIDELIGHTS. THE PRODUCT SUBMITTED FL 10356-R1 IS |
| | ONLY FOR A PAIR OF DOORS NON-IMPACT. MISSING PRODUCT |
| | APPROVALS ARE: |
| | 7A) FIXED OR STOREFRONT WINDOWS/ SIDELIGHTS |
| | 7B) VERTICAL MULLION |
| | 7C ) STORM SHUTTTERS/ PANELS |
| | |
| | 8) STORM SHUTTERS PLEASE PROIDE THE FOLLOWING: FL BLD |
| | CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & EXIST |
| | BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE |
| | INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY |
| | HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT |
| | STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE |
| | ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF |
| | PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |