| 2009-08-31 07:11:52 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | |
| | 1. THE GREASE/SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN NOR MEET CODE REQUIREMENTS. THE CLEANOUT |
| | INDICATED BY THE INLET OF THE GREASE INTERCEPTOR ON THE |
| | GREASE/SANITARY RISER DIAGRAM IS NOT SHOWN ON THE FLOOR |
| | PLAN. TWO WAY CLEANOUTS ARE REQUIRED ON THE INLET AND |
| | OUTLET OF EACH GREASE INTERCEPTOR. THE FLOOR DRAIN IN |
| | THE AREA OF THE WAREWASHER SHALL BE CONNECTED TO THE |
| | GREASE SYSTEM, NOT THE SANITARY SYSTEM. SECTIONS |
| | 106.1.1, 1003.1, 1003.3.1 & UTILITY STANDARDS. |
| | |
| | 2. THE GREASE INTERCEPTOR SHALL BE APPROVED BY THE |
| | UTILITY DEPT. INDUSTRIAL PRETREATMENT/ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY |
| | SUPERVISOR PHONE NUMBER (561) 822-2271, FAX (561) |
| | 822-2279 OR E-MAIL [email protected]. A WRITTEN OR |
| | E-MAIL DETERMINATION IS REQUIRED SHOWING APPROVAL. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |