| 2009-08-27 08:00:20 | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | PROVISOS: |
| | |
| | 1) PROVIDE COMPLIANCE WITH : [F] 904.11.1 MANUAL SYSTEM |
| | OPERATION. A MANUAL ACTUATION DEVICE SHALL BE LOCATED |
| | AT OR NEAR A MEANS OF EGRESS FROM THE COOKING AREA A |
| | MINIMUM OF 10 FEET (3048 MM) AND A MAXIMUM OF 20 FEET |
| | (6096 MM) FROM THE KITCHEN EXHAUST SYSTEM. THE MANUAL |
| | ACTUATION DEVICE SHALL BE INSTALLED NOT MORE THAN 48 |
| | INCHES (1200 MM) OR LESS THAN 42 INCHES (1067 MM) ABOVE |
| | THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD |
| | PROTECTED. THE MANUAL ACTUATION SHALL REQUIRE A MAXIMUM |
| | FORCE OF 40 POUNDS (178 N) AND A MAXIMUM MOVEMENT OF 14 |
| | INCHES (356 MM) TO ACTUATE THE FIRE SUPPRESSION SYSTEM. |
| | |
| | 2) PROVIDE PRODUCT APPROVALS AT TIME OF INSPECTION FOR |
| | SUPPLY, EXHAUST FANS AND ROOF CURBING. |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |