2009-11-23 11:29:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE EQUIPMENT SCHEDULE PER FBC-B 106.3.5.
  
 2. PROVIDE DUCT SIZES AND CFM QUANTITIES ON PLANS. THE
 AIR DISTRIBUTION SYSTEM SHALL BE SIZED AND DESIGNED IN
 ACCORDANCE WITH RECOGNIZED ENGINEERING STANDARDS SUCH
 AS ACCA MANUAL D OR OTHER STANDARDS, IN ACCORDANCE WITH
 FBC-B 610.AB.1, BASED ON THE FOLLOWING:
  
 A. CALCULATION OF THE SUPPLY AIR FOR EACH ROOM SHALL BE
 BASED ON THE GREATER OF THE HEATING LOAD OR SENSIBLE
 COOLING LOAD FOR THAT ROOM.
  
 B. DUCT SIZE SHALL BE DETERMINED BY THE SUPPLY AIR
 REQUIREMENTS OF EACH ROOM, THE AVAILABLE STATIC
 PRESSURE AND THE TOTAL EQUIVALENT LENGTH OF THE VARIOUS
 DUCT RUNS.
  
 C. FRICTION LOSS DATA SHALL CORRESPOND TO THE TYPE OF
 MATERIAL USED IN DUCT CONSTRUCTION.
  
  
  
  
  