Plan Review Notes
Plan Review Notes For Permit 09080581
Permit Number 09080581
Review Stop B
Sequence Number 4
Notes
Date Text
2009-12-15 16:48:05BUILDING PLAN REVIEW
 PERMIT: 09080581
 ADD: 400 N FLAGLER / TENANT B
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 REVISION- REVIEW- 09110611
  
  
 1) SHEET A-4/ DETAIL# 1 & M1.01. PLANS INDICATE A
 PLENUM RETURN.
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF REINSPECTION FEE(S).
  
 PLENUMS- MECHANICAL 602.2.1.5.1, SEPARATION REQUIRED.
 THE FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 PLENUM BY A THERMAL BARRIER COMPLYING WITH SECTION
 2603.4 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 0.5-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250??F (120??C)
 AFTER 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119. THE
 THERMAL BARRIER SHALL BE INSTALLED IN SUCH A MANNER
 THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM
 4880, UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE
 CONCEALED SPACES SHALL COMPLY WITH SECTION 717.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731