Plan Review Notes
Plan Review Notes For Permit 09080581
Permit Number 09080581
Review Stop B
Sequence Number 3
Notes
Date Text
2009-12-01 09:25:12BUILDING PROVISO: 2603.4 THERMAL BARRIER.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.9,
 FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF A
 BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250??F (120??C) AFTER 15 MINUTES OF FIRE EXPOSURE,
 COMPLYING WITH THE STANDARD TIME-TEMPERATURE CURVE OF
 ASTM E 119. THE THERMAL BARRIER SHALL BE INSTALLED IN
 SUCH A MANNER THAT IT WILL REMAIN IN PLACE FOR 15
 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717.
  