2009-10-17 13:34:01REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. PLAN INDICATES 4" ROUND SUPPLY DUCT TO COMPLY WITH
 EXCEPTION #3 PER FBC-M 607.5.3. FIRST, FLEX DUCTS MAY
 NOT PENETRATE ANY FIRE RESISTANCE RATED ASSEMBLY IN
 ACCORDANCE WITH FBC-M 607.7. PLAN STILL SHOWS FLEX DUCT
 PENETRATING THE RATED WALL. ALSO, ANY DUCT PENETRATION
 NOT REQUIRED TO HAVE A FIRE DAMPER SHALL COMPLY WITH
 SECTION 712 OF THE FBC-B PER FBC-M 607.1.1.
 NOTE: THIS ISSUE CAN BE ELIMINATED BY MOVING THE 4"
 ROUND TAP FURTHER DOWNSTREAM IN THE SUPPLY TRUNK TO THE
 OTHER SIDE OF THE RATED WALL, ELIMINATING THE NEED FOR
 THE 4" SUPPLY DUCT TO PENETRATE ANY RATED ASSEMBLIES.
  
 2. OK
  
 3. PROVIDE BOOSTER FAN MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AS WELL AS ANY LISTING INFORMATION PER
 FBC-M 504.6. NO SUCH LISTING COULD BE FOUND. ALSO,
 PROVIDE DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS
 WHICH SHOW PROVISIONS FOR A DRYER BOOSTER FAN AS WELL
 AS FOR INTERLOCKING OF BOSSTER FAN WITH DRYER. CLOTHES
 DRYERS SHALL BE EXHAUSTED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS PER FBC-M 504.1.
 NOTE: IT IS LIKELY THAT A CLOTHES DRYER CAN BE FOUND
 AND SPECIFIED WHICH WILL ALLOW THE LENGTH OF DRYER DUCT
 SHOWN ON PLANS WITHOUT THE USE OF A BOSSTER FAN. IF
 THIS OPTION IS USED, PROVIDE THE DRYER MANUFACTURER'S
 INSTRUCTIONS WHICH SHOW THE ALLOWABLE DUCT LENGTH IN
 ACCORDANCE WITH FBC-M 504.6.1.
  
 4 THROUGH 8: OK
  
 9. THE OCCUPANT LOADS AND VENTILATION RATES SHOWN ON
 PAGE M2.01 VENTILATION CALCULATIONS DO NOT CORRESPOND
 WITH THE VENTILATION REQUIREMENTS BASED ON ASHRAE
 62.1-2004 TABLE 6-1. THE BAR, LOUNGE, FOYER AND
 BILLIARD AREAS SHALL BE CALCULATED WITH AN OCCUPANT
 LOAD OF 100 PEOPLE PER 1000 SQUARE FEET AND AT A
 VENTILATION RATE OF 7.5 CFM/PERSON PLUS 0.18 CFM/SQ FT
 OF AREA.
 NOTE: WHILE IT IS UNDERSTOOD THAT VENTILATION
 CALCULATIONS SHOULD NOT BE PERFORMED BASED ON BUILDING
 CODE OCCUPANT LOADS, IT IS UNNREASONABLE TO PROVIDE
 VENTILATION CALCULATIONS FOR 22 PEOPLE WHEN THE LIFE
 SAFETY PLAN SHOWS AN OCCUPANT LOAD OF 121 PEOPLE.
  
 10. BASED ON COMMENT #9 ABOVE, IT IS LIKELY THAT
 MOTORIZED DAMPERS WILL BE REQUIRED ON OUTSIDE AIR
 INTAKES PER FBC-B 13-409.AB.3.3. ALSO, PROVIDE UPDATED
 COOLING LOAD CALCULATIONS SHOWING INCREASED VENTILATION
 RATES AND PROPERLY SIZED APPLIANCES IN ACCORDANCE WITH
 FBC-M 312.1 AND FBC-B 13-407.AB.1.
  