Plan Review Notes
Plan Review Notes For Permit 09080581
Permit Number 09080581
Review Stop P
Sequence Number 1
Notes
Date Text
2009-08-26 17:03:05DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 2. SHT A-3.0 SHOW COMPLIANCE FOR THE FOLLOWING
 ACCESSIBILITY REQUIREMENTS:
 ___FOR W/C'S
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.5 FLUSH CONTROLS
 C. FIG. 28 W/C SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE
 ___FOR LAVS
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 C. 1104.19.3 LAV SHALL BE MINIMUM 15" OFF THE WALL TO
 THE CENTERLINE OF THE FIXTURE.
 ____FOR SHWRS
 A. 11-4.21.2 CLEAR FLOOR SPACE
 B. 11-4.21.4 GRAB BARS
  
 3. SHT P1.01 KEY NOTES #10 THE CONDENSATE SHALL BE
 PIPED OUT SEPARATELY OUT OF THE BUILDING AND DRAIN INTO
 THE STORM LINE WITH A RELIEF VENT, (GOOSENECK),
 INSTALLED AS THE CONDENSATE EXITS THE BUILDING, OR TO A
 DRYWELL OR A PLANTED AREA. THIS SHALL BE CORRECTED ON
 SHT P-2.01 RISER #1 RAIN WATER AS WELL. SECTION
 314.2.1.
  
 4. SHT P-2.01 RISER #1 RAIN WATER SHOW ALL PIPE SIZES
 AND INDICATE THE SQUARE FOOTAGE BEING DRAIN BY EACH
 DRAIN. TABLE 1106.3.
  
 5. SHTS P-1.01 & P-2.01 A FLOOR DRAIN IS NOT AN
 APPROVED INDIRECT WASTE RECEPTOR FOR THE ICE MACHINE. A
 FLOOR SINK OR HUB DRAIN IS REQUIRED PER SECTIONS 802.3
 & 802.3.2.
  
 6. SHT P-2.01 RISER #3 WATER. THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" FOR THE WASH MACHINE, NOT IN THE
 CEILING AS SHOWN. PDI-WH 201.
  
 7. SHT P-2.01 RISER #2 SANITARY. 3 INCH PIPE IS
 REQUIRED FOR THE WASH MACHINE STACK AND BRANCH DRAIN
 PER SECTION 406.3. PLEASE INDICATE ON RISER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved