| Date |
Text |
| 2009-08-26 17:03:05 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 2. SHT A-3.0 SHOW COMPLIANCE FOR THE FOLLOWING |
| | ACCESSIBILITY REQUIREMENTS: |
| | ___FOR W/C'S |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | C. FIG. 28 W/C SHALL BE 1'6" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE |
| | ___FOR LAVS |
| | A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | B. 11-4.19.5 FAUCETS |
| | C. 1104.19.3 LAV SHALL BE MINIMUM 15" OFF THE WALL TO |
| | THE CENTERLINE OF THE FIXTURE. |
| | ____FOR SHWRS |
| | A. 11-4.21.2 CLEAR FLOOR SPACE |
| | B. 11-4.21.4 GRAB BARS |
| | |
| | 3. SHT P1.01 KEY NOTES #10 THE CONDENSATE SHALL BE |
| | PIPED OUT SEPARATELY OUT OF THE BUILDING AND DRAIN INTO |
| | THE STORM LINE WITH A RELIEF VENT, (GOOSENECK), |
| | INSTALLED AS THE CONDENSATE EXITS THE BUILDING, OR TO A |
| | DRYWELL OR A PLANTED AREA. THIS SHALL BE CORRECTED ON |
| | SHT P-2.01 RISER #1 RAIN WATER AS WELL. SECTION |
| | 314.2.1. |
| | |
| | 4. SHT P-2.01 RISER #1 RAIN WATER SHOW ALL PIPE SIZES |
| | AND INDICATE THE SQUARE FOOTAGE BEING DRAIN BY EACH |
| | DRAIN. TABLE 1106.3. |
| | |
| | 5. SHTS P-1.01 & P-2.01 A FLOOR DRAIN IS NOT AN |
| | APPROVED INDIRECT WASTE RECEPTOR FOR THE ICE MACHINE. A |
| | FLOOR SINK OR HUB DRAIN IS REQUIRED PER SECTIONS 802.3 |
| | & 802.3.2. |
| | |
| | 6. SHT P-2.01 RISER #3 WATER. THE WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" FOR THE WASH MACHINE, NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201. |
| | |
| | 7. SHT P-2.01 RISER #2 SANITARY. 3 INCH PIPE IS |
| | REQUIRED FOR THE WASH MACHINE STACK AND BRANCH DRAIN |
| | PER SECTION 406.3. PLEASE INDICATE ON RISER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |