Plan Review Notes
Plan Review Notes For Permit 09080581
Permit Number 09080581
Review Stop M
Sequence Number 1
Notes
Date Text
2009-09-08 10:18:30REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FLOOR PLAN SHOWS SEVERAL DUCTS PENETRATING RATED
 WALL ASSEMBLIES WITHOUT PROTECTION. EXAMPLES: 4 INCH
 SUPPLY AND EXHAUST AT STAFF RESTROOM B14, 10X3 EXHAUST
 AT GAME ROOM B03. THESE ARE EXAMPLES AND NOT INTENDED
 TO BE AN EXHAUSTIVE LIST. CHECK ALL WALL PENETRATIONS
 FOR REQUIRED PROTECTION OF PENETRATIONS IN ACCORDANCE
 WITH FBC-M 607.1.
  
 2. AHU 3 AND AHU 4 SHARE A COMMON RETURN AIR PLENUM.
 EACH UNIT SHALL BE PROVIDED WITH DUCT SMOKE DETECTORS
 IN ACCORDANCE WITH FBC-M 606.2.2. THE DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH FBC-M 606.4.1.
  
 3. PLANS APPEAR TO SHOW THE DRYER EXHAUST DUCT
 CONNECTING TO AN EXTERIOR, WALL MOUNTED EXHAUST FAN. AN
 EXHAUST FAN USED FOR THIS PURPOSE MUST BE LISTED AND
 LABELED AS A DRYER BOOSTER FAN IN ACCORDANCE WITH FBC-M
 504.6. ALSO, THE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS MUST ALSO INCLUDE THE USE OF AN ADDITIONAL
 FAN (AS WELL AS THE INTERLOCK OF FAN WITH DRYER AS
 CALLED FOR ON THE FAN SCHEDULE) IN ACCORDANCE WITH
 FBC-M 504.1.
  
 4. THE CLOTHES DRYER EXHAUST DUCT IS SHOWN PENETRATING
 A RATED WALL WITH A FIRE DAMPER. FIRE DAMPERS AND ANY
 SIMILAR DEVICES THAT WILL OBSTRUCT THE EXHAUST FLOW
 SHALL BE PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS IN
 ACCORDANCE WITH FBC-M 504.2. THIS DUCT PENETRATION MAY
 BE PROTECTED AS A THROUGH-PENETRATION IN ACCORDANCE
 WITH FBC-B SECTION 712.
  
 5. THE DRYER EXHAUST DUCT SHALL NOT BE LOCATED IN A
 PLENUM IN ACCORDANCE WITH FBC-M 601.5.
  
 6. OUTDOOR EXHAUST FANS AND CONDENSING UNITS SHALL BE
 DESIGNED AND INSTALLED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. PROVIDE MANUFACTURER'S
 DATA FOR FANS AND CONDENSERS SHOWING THESE APPLIANCES
 ARE DESIGNED FOR WIND RESISTANCE. PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR WIND
 RESISTANT INSTALLATION IF APPLICABLE. THERE IS NO
 INSTALLATION DETAIL ON PLANS FOR THE FANS.
 NOTE: THE CONDENSER INSTALLATION DETAIL REFERENCES
 FBC-M 301.13.1, WHICH WAS A PRESCRIPTIVE METHOD OF
 INSTALLATION IN THE 2004 FBC FOR R-3 OCCUPANCIES ONLY.
 THIS PRESCRIPTIVE METHOD IS NOT APPLICABLE. AN
 ENGINEERED DESIGN IS REQUIRED. THE MANUFACTURER'S WIND
 CERTIFICATION MAY CONTAIN SPECIFIC REQUIREMENTS FOR A
 WIND RESISTANCE COMPLIANT INSTALLATION.
  
 7. SUBMIT PRODUCT APPROVALS FOR WALL LOUVERS IN
 ACCORDANCE WITH FAC RULE 9B-72.
  
 8. EMPLOYEE LOUNGE B13 IS SEPARATED FROM THE AHU BY A
 1-HOUR FULL HEIGHT PARTITION. SHOW HOW BALANCED RETURN
 IS TO BE ACHIEVED IN THIS AREA IN ACCORDANCE WITH FBC-M
 601.4.
  
 9. THE VENTILATION CALCULATIONS CLASSIFY ALL AREAS
 SERVED BY THESE SYSTEMS AS "OFFICE." THIS IS NOT
 CORRECT. THESE VENTILATION SYSTEMS SHALL BE DESIGNED TO
 HAVE THE CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW
 RATE DETERMINED IN ACCORDANCE WITH TABLE 403.3 BASED ON
 THE OCCUPANCY OF THE SPACE AND THE OCCUPANT LOAD. THE
 FLOOR PLAN SHOWS SEVERAL DIFFERENT AREAS WITH DIFFERENT
 VENTILATION REQUIREMENTS, SUCH AS (EXAMPLES) THE BAR,
 GAME ROOM, LOUNGE AND FITNESS CENTER. PROVIDE
 SPACE-BY-SPACE VENTILATION CALCULATIONS SHOWING THE
 CORRECT OCCUPANCY CLASSIFICATION, OCCUPANT LOAD AND
 VENTILATION RATE FOR EACH SPACE.
 NOTE: COOLING LOADS MAY ALSO BE AFFECTED BY INCREASED
 VENTILATION.
  
 10. NOTE ON PAGE M2.01 CALLS FOR MANUAL VOLUME DAMPER
 IN LIEU OF A MOTORIZED DAMPER ON THE OUTSIDE AIR
 INTAKES. ACCORDING TO FBC-B 13-409.AB.3.3, A GRAVITY
 OPERATED DAMPER MAY BE USED IN LIEU OF A MOTORIZED
 DAMPER IF THE INTAKE IS LESS THAN 300 CFM. IN ADDITION
 TO THE GRAVITY DAMPER, A MANUAL VOLUME DAMPER IS
 REQUIRED IN ACCORDANCE WITH FBC-B 13-409.AB.1.1.
 NOTE: VENTILATION QUANTITIES ARE LIKELY TO EXCEED 300
 CFM ONCE VENTILATION RATES ARE RECALCULATED PER COMMENT
 #9 ABOVE. IF SO, PROVIDE MOTORIZED VOLUME DAMPERS IN
 ACCORDANCE WITH FBC-B 13-409.AB.3.3.
  
 ENERGY CALCULATIONS: THE METHOD A COMPLIANCE FORM
 SUBMITTED WILL NOT BE REVIEWED FOR THIS PROJECT. THIS
 IS AN ALTERATION TO A PORTION OF AN EXISTING BUILDING
 WHICH DOES NOT MEET THE DEFINITION OF A RENOVATION. AN
 ENERGY CODE COMPLIANCE FORM IS NOT REQUIRED. THE
 DESIGNER IS ONLY REQUIRED TO DEMONSTRATE COMPLIANCE
 WITH THE PRESCRIPTIVE MINIMUM REQUIREMENTS FOR NEW
 SYSTEMS BEING INSTALLED IN ACCORDANCE WITH FBC-B
 13-101.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]