| 2009-09-18 19:27:41 | |
| | |
| | ** DENIED ** |
| | |
| | ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS |
| | SUBMITTED. |
| | |
| | 1A) NOTE: ADDED, PERMIT APPLICATION STATES TENANT SPACE |
| | #C1, HOWEVER PLANS STATE TENANT SPACE *A*. |
| | |
| | 1) NOTE: IN THE PACKAGE THERE ARE SUPPORTING METHOD *A* |
| | WHOLE BUILDING COMPLIANCE ENERGY CALCULATIONS. THIS IS |
| | NOT A WHOLE BUILDING BY DEFINITION. PLEASE ALSO SEE |
| | THAT PLANS ARE SHOWING A SEPARATE METHOD OF COMPLIANCE. |
| | IN FACT PLANS ARE SHOWING PRESCRIPTIVE SPACE BY SPACE |
| | METHOD *B*. |
| | PLEASE SEE SECTIONS NOTED: |
| | |
| | THE LIGHTING PLANS SUBMITTED CLEARLY INDICATE METHOD |
| | *B*. IN FACT THE PLANS STATE COMPLIANCE FOR SPACE BY |
| | SPACE PER 13-415.B.1. PLEASE SEE 13-415.AB.5 OF THE |
| | FBC. THIS SECTION CLEARLY STATES THE FOLLOWING. |
| | |
| | ??? TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE |
| | AMONG PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT |
| | METHOD OF CALCULATION HAS BEEN USED IS NOT PERMITTED*. |
| | |
| | THIS MEANS IT IS NOT PERMISSIBLE TO USE TWO DIFFERENT |
| | METHODS TO SHOW COMPLIANCE. THE SUBMITTED INPUT DATA |
| | REPORT OF THE METHOD *A* IN BOTH CASES IS NOT COMPLETE. |
| | |
| | ** THEREFORE COMPLIANCE WITH PRESCRIPTIVE FOR NEW BEING |
| | INSTALLED IS REQUIRED TO BE MET. |
| | COMPLIANCE FOR METHOD *B* IS SHOWN ON PLANS FOR |
| | LIGHTING PERFORMANCE LEVELS AND IS ACCEPTABLE TO THIS |
| | OFFICE. |
| | 13-415.AB.5, 13-415.B.1, 13-400.0.B.4. PLEASE TAKE A |
| | LOOK AT THE LAST SENTENCE FOR * BUILDINGS NOT MEETING |
| | THE DEFINITION OF A RENOVATION. |
| | |
| | ** PLANS INDICATE ALLOWANCES FOR TWO AHU CLOSETS, YET |
| | THE PLANS ONLY CONTAIN ONE. |
| | |
| | ** AT SOME POINT THE FIXTURE K TYPE WILL BE REQUIRED TO |
| | BE IDENTIFIED ON FINAL PLANS OF RECORD. |
| | |
| | |
| | ** BASED ON THE ABOVE AND THE INFORMATION NOT YET |
| | SHOWN, THE LIGHTING PERFORMANCE CALCULATIONS ARE OVER |
| | THE ALLOWANCES OF THE FLORIDA ENERGY CODE. |
| | |
| | 2) NOTE: ONE OF THE COPIES OF THE SUBMITTED METHOD *A* |
| | CALCULATIONS ARE PHOTO-COPIES OF SIGNED DOCUMENTS. THIS |
| | IS NOT PERMITTED PER FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: COMPLIANCE FOR NEW LIGHTING CONTROLS BEING |
| | INSTALLED SHALL MEET 13-415.AB.1.1,.1.2 AND .1.3. |
| | PLEASE SEE 13-415.AB.1.3 SPECIFICALLY AS OTHER LIGHTING |
| | SUCH AS TRACK LIGHTING WHICH IS NOT PART OF THE GENERAL |
| | LIGHTING SHALL HAVE SEPARATE CONTROLS. |
| | PLANS INDICATE SOME SORT OF SWITCHES HOWEVER THERE IS |
| | NOT ENOUGH INFORMATION FOR PROPOSED SYSTEM. ARE THESE |
| | OVER RIDES? NO INFORMATION ON PROPOSED SYSTEM, TIMES OF |
| | OVER RIDES, ETC |
| | |
| | 4) NOTE: IS THE STAIRS AN EGRESS PATH BY DEFINITION? IF |
| | SO, PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 FOR MINIMUM |
| | LIGHTING LEVELS REQUIRED. |
| | |
| | 5) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES 15/20AMP |
| | IN KITCHEN AREA SHALL BE GFI/ GFI PROTECTED. THIS IS |
| | REQUIRED WHETHER OR NOT RECEPTACLES SERVES A COUNTER |
| | SPACE OR DEDICATED EQUIPMENT. |
| | |
| | 6) NOTE: PLEASE SEE 422.13 FOR STORAGE TYPE OF WATER |
| | HEATERS AND REQUIRED MINIMUM 125% LOAD TO BE FIGURED |
| | FOR CALCULATIONS OF SERVICES AND FEEDERS. |
| | ** SEE 2005 NEC COMMENTARY LAST SENTENCE. THIS IS |
| | CONSIDERED A CONTINUOUS LOAD. |
| | |
| | 7) NOTE: PLEASE ALSO SHOW LOAD CALCULATION COMPLIANCE |
| | FOR SIZING SERVICE FEEDERS PER 220.43B |
| | |
| | 9) NOTE: DISCONNECT FOR EXHAUST FAN IS MISSING. PLANS |
| | STATE TO TIME CLOCK FOR CONTROL? |
| | PLEASE SEE 430.102B |
| | |
| | 10) NOTE: DISCONNECT FOR CU DOES NOT MEET 110.26 FOR |
| | MINIMUM CLEARANCES. |
| | |
| | 11) NOTE: PLANS APPEAR TO SHOW HOUSE PANEL IN THIS |
| | TENANT SPACE. WHAT IS THIS TENANT SPACE A PART OF? BASE |
| | BUILDING? |
| | |
| | ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT |
| | INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS |
| | REQUIRED. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |