| Notes |
| Date |
Text |
| 2009-10-02 09:00:44 | ** REDLINED PLANS ** | | | | | | 1) NOTE: THE LIGHTING CONTROLS FOR ELECTRICAL ROOM | | | SHALL NOT BE BY AUTOMATED CONTROLS ALONE. NEC 110.26D. | | | | | | 2) NOTE: ALL METERS AFTER THE FIRST MEANS OF DISCONNECT | | | SHALL HAVE A FLOATING NEUTRAL KIT. 250.6,250.24. | | | IF A FLOATING NEUTRAL KIT IS NOT INSTALLED, THE | | | EQUIPMENT GROUNDING CONDUCTOR WOULD PARALLEL THE | | | NEUTRAL CREATING OBJECTIONABLE CURRENTS. | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|