2009-10-02 09:00:44** REDLINED PLANS **
  
 1) NOTE: THE LIGHTING CONTROLS FOR ELECTRICAL ROOM
 SHALL NOT BE BY AUTOMATED CONTROLS ALONE. NEC 110.26D.
  
 2) NOTE: ALL METERS AFTER THE FIRST MEANS OF DISCONNECT
 SHALL HAVE A FLOATING NEUTRAL KIT. 250.6,250.24.
 IF A FLOATING NEUTRAL KIT IS NOT INSTALLED, THE
 EQUIPMENT GROUNDING CONDUCTOR WOULD PARALLEL THE
 NEUTRAL CREATING OBJECTIONABLE CURRENTS.
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  