2009-09-18 18:41:58 
  
 ** DENIED **
  
 ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS
 SUBMITTED.
  
 1A) NOTE: ADDED, PERMIT APPLICATION STATES TENANT SPACE
 #C1, HOWEVER PLANS STATE TENANT SPACE *A*.
  
 1) NOTE: IN THE PACKAGE THERE ARE SUPPORTING METHOD *A*
 WHOLE BUILDING COMPLIANCE ENERGY CALCULATIONS. THIS IS
 NOT A WHOLE BUILDING BY DEFINITION. PLEASE ALSO SEE
 THAT PLANS ARE SHOWING A SEPARATE METHOD OF COMPLIANCE.
 IN FACT PLANS ARE SHOWING PRESCRIPTIVE SPACE BY SPACE
 METHOD *B*.
 PLEASE SEE SECTIONS NOTED:
  
 THE LIGHTING PLANS SUBMITTED CLEARLY INDICATE METHOD
 *B*. IN FACT THE PLANS STATE COMPLIANCE FOR SPACE BY
 SPACE PER 13-415.B.1. PLEASE SEE 13-415.AB.5 OF THE
 FBC. THIS SECTION CLEARLY STATES THE FOLLOWING.
  
 * TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE AMONG
 PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT METHOD
 OF CALCULATION HAS BEEN USED IS NOT PERMITTED*.
  
 THIS MEANS IT IS NOT PERMISSIBLE TO USE TWO DIFFERENT
 METHODS TO SHOW COMPLIANCE. THE SUBMITTED INPUT DATA
 REPORT OF THE METHOD *A* IN BOTH CASES IS NOT COMPLETE.
  
 ** THEREFORE COMPLIANCE WITH PRESCRIPTIVE FOR NEW BEING
 INSTALLED IS REQUIRED TO BE MET.
 COMPLIANCE FOR METHOD *B* IS SHOWN ON PLANS FOR
 LIGHTING PERFORMANCE LEVELS AND IS ACCEPTABLE TO THIS
 OFFICE.
 13-415.AB.5, 13-415.B.1, 13-400.0.B.4. PLEASE TAKE A
 LOOK AT THE LAST SENTENCE FOR * BUILDINGS NOT MEETING
 THE DEFINITION OF A RENOVATION.
  
 ** IMPORTANT. PLANS STATE FUTURE DISPLAY CASES WHICH
 ARE GOING TO BE LIGHTED. PLEASE SEE 13-415.AB.5 AS
 THESE LIGHTED CASED SHALL BE FIGURED INTO THE TOTAL
 ALLOWANCES.
 THE REVISED CODE DOES NOT CONTAIN DISPLAY AREA
 ALLOWANCES.
  
 ** THE SECURITY OFFICE IS AN OFFICE USE NOT OTHER AS
 SHOWN. 1.1, NOT 1.5.
 ** THERE IS NOT CONFERENCE ROOM ON PLANS. ALLOWANCE MAY
 NOT BE USED.
 ** WORK/COPY ROOM MAY NOT USE 1.5, THIS IS OFFICE.
  
 ** BASED ON THE ABOVE AND THE INFORMATION NOT YET
 SHOWN, THE LIGHTING PERFORMANCE CALCULATIONS ARE
 SUBSTANTIALLY OVER THE ALLOWANCES OF THE FLORIDA ENERGY
 CODE.
  
 2) NOTE: ONE OF THE COPIES OF THE SUBMITTED METHOD *A*
 CALCULATIONS ARE PHOTO-COPIES OF SIGNED DOCUMENTS. THIS
 IS NOT PERMITTED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: COMPLIANCE FOR NEW LIGHTING CONTROLS BEING
 INSTALLED SHALL MEET 13-415.AB.1.1,.1.2 AND .1.3.
 PLEASE SEE 13-415.AB.1.3 SPECIFICALLY AS OTHER LIGHTING
 SUCH AS TRACK LIGHTING WHICH IS NOT PART OF THE GENERAL
 LIGHTING SHALL HAVE SEPARATE CONTROLS.
 THIS IS ALSO FOR FUTURE DISPLAY CASES WHICH ARE ALSO
 REQUIRED TO BE PART OF THE AUTOMATED LIGHTING CONTROLS
 INCLUDING SEPARATE CONTROLS.
  
 4) NOTE: PLANS CONTAIN ELECTRICAL FOR OTHER FUTURE
 TENANT SPACE YET THIS SPACE IS ALREADY SUBMITTED FOR
 PERMIT. RECORD PLANS WOULD NOT CONTAIN ELECTRICAL WHICH
 IS NOT PART OF THE APPLIED SCOPE OF WORK.
  
 5) NOTE: EXTERIOR LIGHTING CONTROLS AS NOTED FOR SHELL
 SHALL MEET 13-415.AB.1.4. MUST BE PHOTO-SENSOR TYPE OR
 ASTRONOMICAL TIME CLOCK WITH MINIMUM OF 10HRS BACK UP.
 IT IS PERMISSIBLE TO HAVE BOTH.
  
 6) NOTE: SHOW WINDOW RECEPTACLES REQUIRED PER 210.62
  
 7) NOTE: LOAD CALCULATIONS NEED TO COMPLY WITH NEC FOR
 SHOW WINDOWS FIGURED PER 220.14G AND 220.43A.
 PLEASE ALSO INDICATE ALL CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%. IF ALREADY FIGURED INTO SERVICE
 THEN PLEASE SHOW WHERE OR NOTE THIS WAS DONE ON PLANS.
 215.3, 230.42 ETC
  
 8) NOTE: PLEASE ALSO SHOW LOAD CALCULATION COMPLIANCE
 FOR SIZING SERVICE FEEDERS PER 220.43B
  
 9) NOTE: DISCONNECT LOCATION FOR CU DOES NOT MEET
 110.26.
  
 10) NOTE: PLEASE SEE FBC 11-4.28.1.3. THERE IS A
 HORN/STROBE DEVICE ON FA SHEET WHICH IS MISSING CANDELA
 LEVEL. SEE SECTION NOTED FOR MINIMUM REQUIRED.
 PLEASE ALSO SEE 11-4.28.1 AND .2.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717