| 2009-09-18 18:41:58 | |
| | |
| | ** DENIED ** |
| | |
| | ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS |
| | SUBMITTED. |
| | |
| | 1A) NOTE: ADDED, PERMIT APPLICATION STATES TENANT SPACE |
| | #C1, HOWEVER PLANS STATE TENANT SPACE *A*. |
| | |
| | 1) NOTE: IN THE PACKAGE THERE ARE SUPPORTING METHOD *A* |
| | WHOLE BUILDING COMPLIANCE ENERGY CALCULATIONS. THIS IS |
| | NOT A WHOLE BUILDING BY DEFINITION. PLEASE ALSO SEE |
| | THAT PLANS ARE SHOWING A SEPARATE METHOD OF COMPLIANCE. |
| | IN FACT PLANS ARE SHOWING PRESCRIPTIVE SPACE BY SPACE |
| | METHOD *B*. |
| | PLEASE SEE SECTIONS NOTED: |
| | |
| | THE LIGHTING PLANS SUBMITTED CLEARLY INDICATE METHOD |
| | *B*. IN FACT THE PLANS STATE COMPLIANCE FOR SPACE BY |
| | SPACE PER 13-415.B.1. PLEASE SEE 13-415.AB.5 OF THE |
| | FBC. THIS SECTION CLEARLY STATES THE FOLLOWING. |
| | |
| | * TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE AMONG |
| | PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT METHOD |
| | OF CALCULATION HAS BEEN USED IS NOT PERMITTED*. |
| | |
| | THIS MEANS IT IS NOT PERMISSIBLE TO USE TWO DIFFERENT |
| | METHODS TO SHOW COMPLIANCE. THE SUBMITTED INPUT DATA |
| | REPORT OF THE METHOD *A* IN BOTH CASES IS NOT COMPLETE. |
| | |
| | ** THEREFORE COMPLIANCE WITH PRESCRIPTIVE FOR NEW BEING |
| | INSTALLED IS REQUIRED TO BE MET. |
| | COMPLIANCE FOR METHOD *B* IS SHOWN ON PLANS FOR |
| | LIGHTING PERFORMANCE LEVELS AND IS ACCEPTABLE TO THIS |
| | OFFICE. |
| | 13-415.AB.5, 13-415.B.1, 13-400.0.B.4. PLEASE TAKE A |
| | LOOK AT THE LAST SENTENCE FOR * BUILDINGS NOT MEETING |
| | THE DEFINITION OF A RENOVATION. |
| | |
| | ** IMPORTANT. PLANS STATE FUTURE DISPLAY CASES WHICH |
| | ARE GOING TO BE LIGHTED. PLEASE SEE 13-415.AB.5 AS |
| | THESE LIGHTED CASED SHALL BE FIGURED INTO THE TOTAL |
| | ALLOWANCES. |
| | THE REVISED CODE DOES NOT CONTAIN DISPLAY AREA |
| | ALLOWANCES. |
| | |
| | ** THE SECURITY OFFICE IS AN OFFICE USE NOT OTHER AS |
| | SHOWN. 1.1, NOT 1.5. |
| | ** THERE IS NOT CONFERENCE ROOM ON PLANS. ALLOWANCE MAY |
| | NOT BE USED. |
| | ** WORK/COPY ROOM MAY NOT USE 1.5, THIS IS OFFICE. |
| | |
| | ** BASED ON THE ABOVE AND THE INFORMATION NOT YET |
| | SHOWN, THE LIGHTING PERFORMANCE CALCULATIONS ARE |
| | SUBSTANTIALLY OVER THE ALLOWANCES OF THE FLORIDA ENERGY |
| | CODE. |
| | |
| | 2) NOTE: ONE OF THE COPIES OF THE SUBMITTED METHOD *A* |
| | CALCULATIONS ARE PHOTO-COPIES OF SIGNED DOCUMENTS. THIS |
| | IS NOT PERMITTED PER FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: COMPLIANCE FOR NEW LIGHTING CONTROLS BEING |
| | INSTALLED SHALL MEET 13-415.AB.1.1,.1.2 AND .1.3. |
| | PLEASE SEE 13-415.AB.1.3 SPECIFICALLY AS OTHER LIGHTING |
| | SUCH AS TRACK LIGHTING WHICH IS NOT PART OF THE GENERAL |
| | LIGHTING SHALL HAVE SEPARATE CONTROLS. |
| | THIS IS ALSO FOR FUTURE DISPLAY CASES WHICH ARE ALSO |
| | REQUIRED TO BE PART OF THE AUTOMATED LIGHTING CONTROLS |
| | INCLUDING SEPARATE CONTROLS. |
| | |
| | 4) NOTE: PLANS CONTAIN ELECTRICAL FOR OTHER FUTURE |
| | TENANT SPACE YET THIS SPACE IS ALREADY SUBMITTED FOR |
| | PERMIT. RECORD PLANS WOULD NOT CONTAIN ELECTRICAL WHICH |
| | IS NOT PART OF THE APPLIED SCOPE OF WORK. |
| | |
| | 5) NOTE: EXTERIOR LIGHTING CONTROLS AS NOTED FOR SHELL |
| | SHALL MEET 13-415.AB.1.4. MUST BE PHOTO-SENSOR TYPE OR |
| | ASTRONOMICAL TIME CLOCK WITH MINIMUM OF 10HRS BACK UP. |
| | IT IS PERMISSIBLE TO HAVE BOTH. |
| | |
| | 6) NOTE: SHOW WINDOW RECEPTACLES REQUIRED PER 210.62 |
| | |
| | 7) NOTE: LOAD CALCULATIONS NEED TO COMPLY WITH NEC FOR |
| | SHOW WINDOWS FIGURED PER 220.14G AND 220.43A. |
| | PLEASE ALSO INDICATE ALL CONTINUOUS LOADS AND LARGEST |
| | MOTOR LOADS AT 125%. IF ALREADY FIGURED INTO SERVICE |
| | THEN PLEASE SHOW WHERE OR NOTE THIS WAS DONE ON PLANS. |
| | 215.3, 230.42 ETC |
| | |
| | 8) NOTE: PLEASE ALSO SHOW LOAD CALCULATION COMPLIANCE |
| | FOR SIZING SERVICE FEEDERS PER 220.43B |
| | |
| | 9) NOTE: DISCONNECT LOCATION FOR CU DOES NOT MEET |
| | 110.26. |
| | |
| | 10) NOTE: PLEASE SEE FBC 11-4.28.1.3. THERE IS A |
| | HORN/STROBE DEVICE ON FA SHEET WHICH IS MISSING CANDELA |
| | LEVEL. SEE SECTION NOTED FOR MINIMUM REQUIRED. |
| | PLEASE ALSO SEE 11-4.28.1 AND .2. |
| | |
| | |
| | ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT |
| | INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS |
| | REQUIRED. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |