| 2009-08-24 17:36:02 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 EXISTING BUILDING |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 104.1.1, (BLDG) & 403.1, (PLMG). INDICATE THE |
| | TOTAL SQUARE FOOTAGE OF THE FIRST FLOOR AND SHOW THE |
| | REQUIRED FIXTURES FOR THE FLOOR. TWO FIXTURES, (WATER |
| | CLOSETS HAVE BEEN DELETED). |
| | |
| | 2. SHT A1.1 THE ACCESSIBLE TOILET STALL IN THE WOMEN'S |
| | TOILET ROOM DOES NOT COMPLY WITH FIGURE 30E. A LAV IS |
| | REQUIRED IN THE STALL. PER SECTION 11-4.1.6(1)(B) IF |
| | EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, |
| | THEN EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA |
| | SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION |
| | 11-4.1.1 TO SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR |
| | NEW CONSTRUCTION. |
| | |
| | 3. SHT A2.1 DETAIL A1 DOES NOT COMPLY WITH FIGURE 31 |
| | FOR THE CLEARANCE. THE BOTTOM OF THEREMOVABLE PANEL |
| | SHALL BE A MAXIMUM 6 INCHES OFF THE WALL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |