Plan Review Notes
Plan Review Notes For Permit 09080523
Permit Number 09080523
Review Stop M
Sequence Number 1
Notes
Date Text
2009-09-09 16:25:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SUBMIT TWO COMPLETE SETS OF DOCUMENTATION FOR PERMIT
 IN ACCORDANCE WITH FBC 106.1.
  
 2. THE VALUE AND SCOPE OF WORK PROPOSED CONSTITUTES A
 RENOVATION IN ACCORDANCE WITH FBC-B 13-202. RENOVATED
 BUILDINGS SHALL MEET THE PRESCRIPTIVE REQUIREMENTS
 CONTAINED IN METHOD B OF SUBCHAPTER 13-6 FOR
 RESIDENTIAL APPLICATIONS OF THE CODE FOR INSULATION,
 HVAC SYSTEMS AND EXTERIOR ENVELOPE (WINDOWS) FOR THOSE
 COMPONENTS BEING RETROFITTED OR REPLACED IN ACCORDANCE
 WITH FBC-B 13-101.2.3. DEMONSTRATE COMPLIANCE WITH
 THESE REQUIREMENTS.
  
 3. A COOLING AND HEATING LOAD CALCULATION SHALL BE
 PERFORMED ON THE BUILDING AND SHALL BE ATTACHED TO THE
 CODE COMPLIANCE FORM SUBMITTED WHEN APPLICATION IS MADE
 FOR A BUILDING PERMIT IN ACCORDANCE WITH FBC-B
 13-607.AB.1.
  
 4. A SEPARATE ELECTRICAL PERMIT IS REQUIRED.
  