| Plan Review Notes For Permit 09080516 |
| Permit Number |
09080516 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-09-17 16:47:55 | ****CORRECTIONS**** | | | REVISION #1 | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | THIS PERMIT WAS ISSUED WITH PROVISOS WHICH WHERE NOT | | | ADDRESSED: | | | | | | 1. REVISE STRUCTURAL DETAILS: | | | SHEATHING TO COMPLY WITH MINIMUM REQUIREMENT OF FBC R | | | TABLE 803.1 - SHEATHING WAS CHANGED FROM 7/16" OSB TO | | | 5/32. IT IS NOT CLEAR HOW MAKING THE SHEATHING LESS | | | THAN 1/4" MAKES IT COMPLY WITH THE 1/2" MINIMUM | | | REQUIREMENT. PLEASE HAVE THE ENGINEER CONTACT ME IF | | | CLARIFICATION IS REQUIRED. | | | | | | ENGINEER TO INCORPORATE CHANGES INTO PLAN - THIS WAS | | | NOT ADDRESSED. PLEASE HAVE ENGINEER INCORPORATE THE | | | CHANGES TO THE DESIGN INTO HIS PLAN. | | | | | | |
|