Plan Review Notes
Plan Review Notes For Permit 09080497
Permit Number 09080497
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-25 12:31:58ELECTRICAL PLAN REVIEW
 PERMIT: 09080497
 ADD: 734 20TH ST
 CONT: BLACK STREET ENTERPRISES, LLC
 TEL: (561)931-5707
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2005 NEC
  
 AUGUST 25/2009
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS ARE NOT CLEAR AS IF THE ELECTRICAL RISER (NEW
 SERVICE) WILL BE REPLACED AS PART OF THE ELECTRICAL
 SCOPING OF THIS PERMIT, THIS INFORMATION WILL EFFECT
 THE OUTCOME OF THIS REVIEW.
  
 1A) IF THE EXISTING ELECTRICAL SERVICE IS TO BE USED,
 THEN SECTION 220.83 (B) OR 100% OF THE HEATING AND A/C
 LOADS MUST BE USED.
  
 2) RISER DIAGRAM IS MISSING GROUNDING CONDUCTOR SIZING,
 TABLE 250.122 MINIMUM SIZE EQUIPMENT GROUNDING
 CONDUCTORS FOR GROUNDING RACEWAY AND EQUIPMENT,
 100 AMP PANEL / # 8 COPPER AWG.
  
 3) 422.13 STORAGE-TYPE WATER HEATERS A FIXED
 STORAGE-TYPE WATER HEATER THAT HAS A CAPACITY OF 450 L
 (120 GAL) OR LESS SHALL BE CONSIDERED A CONTINUOUS
 LOAD.
 THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING.
  
 4) NEW MECHANICAL DISCONNECT FOR COMPRESSOR IS
 INDICATED BEHIND THE COMPRESSOR. PLEASE REVIEW SECTION
 440.63 DISCONNECTING MEANS AN APPROVED MANUALLY
 OPERABLE DISCONNECTING MEANS IS INSTALLED IN A READILY
 ACCESSIBLE LOCATION WITHIN SIGHT.
  
 5) THE NEW WALL OF THE AIR HANDLIER CLOSET ADJACENT TO
 BEDROOM # 1 IS MISSING OUTLETS,WHEN NEW WALL SECTIONS
 ARE OVER 2'0" LONG, SEE SECTION 210.52(A)(2)(1) ANY
 SPACE (2 FT) OR MORE IN WIDTH (INCLUDING SPACE MEASURED
 AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR LINE BY
 DOORWAYS, FIREPLACES, AND SIMILAR OPENINGS .
  
 6) PLEASE NOTE THE LOCATION OF SMOKE ALARM LOCATED
 OUTSIDE OF THE BEDROOMS, PLEASE SEE NFPA 72
 REQUIREMENTS AS WELL AS MANUFACTURERS LOCATION AS TO
 SUPPLY / RETURN AIR GRILLES AS WELL AS BATHROOM
 LOCATIONS.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 SFP-100
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  