| 2009-08-25 12:31:58 | ELECTRICAL PLAN REVIEW |
| | PERMIT: 09080497 |
| | ADD: 734 20TH ST |
| | CONT: BLACK STREET ENTERPRISES, LLC |
| | TEL: (561)931-5707 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | 2005 NEC |
| | |
| | AUGUST 25/2009 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS ARE NOT CLEAR AS IF THE ELECTRICAL RISER (NEW |
| | SERVICE) WILL BE REPLACED AS PART OF THE ELECTRICAL |
| | SCOPING OF THIS PERMIT, THIS INFORMATION WILL EFFECT |
| | THE OUTCOME OF THIS REVIEW. |
| | |
| | 1A) IF THE EXISTING ELECTRICAL SERVICE IS TO BE USED, |
| | THEN SECTION 220.83 (B) OR 100% OF THE HEATING AND A/C |
| | LOADS MUST BE USED. |
| | |
| | 2) RISER DIAGRAM IS MISSING GROUNDING CONDUCTOR SIZING, |
| | TABLE 250.122 MINIMUM SIZE EQUIPMENT GROUNDING |
| | CONDUCTORS FOR GROUNDING RACEWAY AND EQUIPMENT, |
| | 100 AMP PANEL / # 8 COPPER AWG. |
| | |
| | 3) 422.13 STORAGE-TYPE WATER HEATERS A FIXED |
| | STORAGE-TYPE WATER HEATER THAT HAS A CAPACITY OF 450 L |
| | (120 GAL) OR LESS SHALL BE CONSIDERED A CONTINUOUS |
| | LOAD. |
| | THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN |
| | ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120 |
| | GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION |
| | REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND |
| | CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE |
| | WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT |
| | DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED |
| | TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT |
| | RATING. |
| | |
| | 4) NEW MECHANICAL DISCONNECT FOR COMPRESSOR IS |
| | INDICATED BEHIND THE COMPRESSOR. PLEASE REVIEW SECTION |
| | 440.63 DISCONNECTING MEANS AN APPROVED MANUALLY |
| | OPERABLE DISCONNECTING MEANS IS INSTALLED IN A READILY |
| | ACCESSIBLE LOCATION WITHIN SIGHT. |
| | |
| | 5) THE NEW WALL OF THE AIR HANDLIER CLOSET ADJACENT TO |
| | BEDROOM # 1 IS MISSING OUTLETS,WHEN NEW WALL SECTIONS |
| | ARE OVER 2'0" LONG, SEE SECTION 210.52(A)(2)(1) ANY |
| | SPACE (2 FT) OR MORE IN WIDTH (INCLUDING SPACE MEASURED |
| | AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR LINE BY |
| | DOORWAYS, FIREPLACES, AND SIMILAR OPENINGS . |
| | |
| | 6) PLEASE NOTE THE LOCATION OF SMOKE ALARM LOCATED |
| | OUTSIDE OF THE BEDROOMS, PLEASE SEE NFPA 72 |
| | REQUIREMENTS AS WELL AS MANUFACTURERS LOCATION AS TO |
| | SUPPLY / RETURN AIR GRILLES AS WELL AS BATHROOM |
| | LOCATIONS. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | SFP-100 |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |