2009-08-25 15:18:42BUILDING PLAN REVIEW
 PERMIT: 09080497
 ADD: 734 20TH ST
 CONT: BLACK STREET ENTERPRISES, LLC
 TEL: (561)931-5707
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
  
 AUGUST 25/2009
 1ST REVIEW
 ACTION: DENIED
  
 1) ISSUES WITH GLAZED WINDOW UNITS:
 1A) SUBMITTED ALONG WITH THE PERMIT APPLICATION WAS A
 CLOSED SHUTTER PERMIT# 08080461 AN ATTACHED COPY IS
 ENCLOSED. PLEASE NOTE THAT THE BEDROOM WINDOWS UNDER
 THE PLANS SUBMITTED INDICATE THE BEDROOM WINDOW SILLS
 TO BE LOWERED FOR EMERGENCY EGRESS REQUIREMENTS. THE
 SHUTTERS FOR THE BEDROOM WINDOWS WILL NOW BE TO SHORT
 SINCE THEY WERE INDICATED AS BEING INSTALLED VERTICALLY
 TTHE SHUTTER WILL NOT BE ATTACHED AT THE NEW SILL
 HEIGHT. PLEASE ALSO SUBMIT NEW SHUTTER SCHEDULE FOR
 THESE WINDOWS AND PRODUCT APPROVAL FOR STORM SHUTTERS
 OR IF SHUTTERS TO BE INSTALLED HORIZONTALLY THEN SUBMIT
 A NEW SHUTTER SCHEDULE FOR ALL WINDOWS WHERE THE WINDOW
 SILL IS GOING TO BE LOWERED.
  
 1B) PLEASE ALSO REVIEW THE SHUTTER KEY PLAN VERSES THE
 FLOOR PLAN BEDROOM# 3 ON THE SHUTTER KEY PLAN INDICATES
 WINDOW 2 & 3 IN THE WALL WHERE THE FLOOR PLAN ONLY
 INDICCATES ONE WINDOW, PLEASE ALSO SEE THE SAME
 CONDITION HAPPENS IN THE LIVING ROOM WITH WINDOWS 7& 8.
 PLEASE REVIEW AND INDICATE COMPLIANCE WITH THE LARGE
 MISSILE IMPACT REQUIREMENTS.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 2) THE NEW A/C CLOSET PLEASE PROVIDE A WALL SECTION
 INDICATING TMATERIALS TO BE USED IN CREATING THIS NEW
 WALL. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) PLANS ALSO INDICATE THE REMOVAL OF CONCRETE SLAB AND
 REPOURING OF SLAB, PLEASE INDICATE COMPLIANCE WITH
 TERMITE TREATMET 1503.3.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN SPOUTS SHALL
 DISCHARGE AT LEAST 1 FT. AWAY FROM THE STRUCTURE
 SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved