| 2009-08-25 15:18:42 | BUILDING PLAN REVIEW |
| | PERMIT: 09080497 |
| | ADD: 734 20TH ST |
| | CONT: BLACK STREET ENTERPRISES, LLC |
| | TEL: (561)931-5707 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | |
| | AUGUST 25/2009 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ISSUES WITH GLAZED WINDOW UNITS: |
| | 1A) SUBMITTED ALONG WITH THE PERMIT APPLICATION WAS A |
| | CLOSED SHUTTER PERMIT# 08080461 AN ATTACHED COPY IS |
| | ENCLOSED. PLEASE NOTE THAT THE BEDROOM WINDOWS UNDER |
| | THE PLANS SUBMITTED INDICATE THE BEDROOM WINDOW SILLS |
| | TO BE LOWERED FOR EMERGENCY EGRESS REQUIREMENTS. THE |
| | SHUTTERS FOR THE BEDROOM WINDOWS WILL NOW BE TO SHORT |
| | SINCE THEY WERE INDICATED AS BEING INSTALLED VERTICALLY |
| | TTHE SHUTTER WILL NOT BE ATTACHED AT THE NEW SILL |
| | HEIGHT. PLEASE ALSO SUBMIT NEW SHUTTER SCHEDULE FOR |
| | THESE WINDOWS AND PRODUCT APPROVAL FOR STORM SHUTTERS |
| | OR IF SHUTTERS TO BE INSTALLED HORIZONTALLY THEN SUBMIT |
| | A NEW SHUTTER SCHEDULE FOR ALL WINDOWS WHERE THE WINDOW |
| | SILL IS GOING TO BE LOWERED. |
| | |
| | 1B) PLEASE ALSO REVIEW THE SHUTTER KEY PLAN VERSES THE |
| | FLOOR PLAN BEDROOM# 3 ON THE SHUTTER KEY PLAN INDICATES |
| | WINDOW 2 & 3 IN THE WALL WHERE THE FLOOR PLAN ONLY |
| | INDICCATES ONE WINDOW, PLEASE ALSO SEE THE SAME |
| | CONDITION HAPPENS IN THE LIVING ROOM WITH WINDOWS 7& 8. |
| | PLEASE REVIEW AND INDICATE COMPLIANCE WITH THE LARGE |
| | MISSILE IMPACT REQUIREMENTS. |
| | |
| | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 2) THE NEW A/C CLOSET PLEASE PROVIDE A WALL SECTION |
| | INDICATING TMATERIALS TO BE USED IN CREATING THIS NEW |
| | WALL. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 3) PLANS ALSO INDICATE THE REMOVAL OF CONCRETE SLAB AND |
| | REPOURING OF SLAB, PLEASE INDICATE COMPLIANCE WITH |
| | TERMITE TREATMET 1503.3.6 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN SPOUTS SHALL |
| | DISCHARGE AT LEAST 1 FT. AWAY FROM THE STRUCTURE |
| | SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL |
| | EXTENSIONS, OR SPLASH BLOCKS. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |