| Notes |
| Date |
Text |
| 2009-09-01 17:46:40 | **PROVISO** | | | 1. DUCT SMOKE DETECTORS REQUIRED ON ALL THREE AIR | | | HANDLERS PER FBC-M 606.2.2. CONNECT DETECTORS TO | | | BUILDING FIRE ALARM SYSTEM PER FBC-M 606.4. REVISE | | | PLANS AND RESUBMIT, SHOWING THIS CORRECTION. | | | | | | 2. OUTSIDE AIR INTAKE TO BE INSTALLED PER ATTACHED NOA, | | | NOT THE DETAIL ON PAGE M2.01. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|