Plan Review Notes
Plan Review Notes For Permit 09080496
Permit Number 09080496
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-08-27 13:52:33*****DENIED*****
  
 PLAN SHEET FS1.01 WAS STAMPED, INITIALED, AND DATED;
 HOWEVER THE FOLLOWING COMMENTS NEED TO BE SATISFIED FOR
 FIRE REVIEW APPROVAL:
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241- 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. BE ADVISED OF THE CURRENTLY ADOPTED CODE EDITIONS AS
 FOLLOWS: FLORIDA BUILDING CODE - 2007 EDITION, FLORIDA
 FIRE PREVENTION CODE - 2007 EDITION, .......ON SHEET
 A1.01, AMEND APPLICABLE CODES
  
 4. ON SHEET A1.01, FIRE EXTINGUISHERS ARE SHOWN IN
 ROOMS 312, 315, AND 328; HOWEVER ON SHEET A1.03, A FIRE
 EXTINGUISHER IS SHOWN IN ONLY ROOM 315........THESE
 SHEETS SHOULD CORRELATE
  
 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. VERITY/CLARIFY THAT DOORS CLOSERS WILL BE REQUIRED
 FOR DOORS 300 AND 317.................ON SHEET A3.01,
 INCLUDE IN DOOR SCEDULE - REMARKS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722