| Plan Review Notes For Permit 09080496 |
| Permit Number |
09080496 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-27 13:52:33 | *****DENIED***** | | | | | | PLAN SHEET FS1.01 WAS STAMPED, INITIALED, AND DATED; | | | HOWEVER THE FOLLOWING COMMENTS NEED TO BE SATISFIED FOR | | | FIRE REVIEW APPROVAL: | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241- 2004 | | | EDITION. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 3. BE ADVISED OF THE CURRENTLY ADOPTED CODE EDITIONS AS | | | FOLLOWS: FLORIDA BUILDING CODE - 2007 EDITION, FLORIDA | | | FIRE PREVENTION CODE - 2007 EDITION, .......ON SHEET | | | A1.01, AMEND APPLICABLE CODES | | | | | | 4. ON SHEET A1.01, FIRE EXTINGUISHERS ARE SHOWN IN | | | ROOMS 312, 315, AND 328; HOWEVER ON SHEET A1.03, A FIRE | | | EXTINGUISHER IS SHOWN IN ONLY ROOM 315........THESE | | | SHEETS SHOULD CORRELATE | | | | | | 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS | | | AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6. VERITY/CLARIFY THAT DOORS CLOSERS WILL BE REQUIRED | | | FOR DOORS 300 AND 317.................ON SHEET A3.01, | | | INCLUDE IN DOOR SCEDULE - REMARKS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|