| 2009-08-20 15:08:08 | DENIED |
| | REFERENCE: |
| | FBC-2007 W 2009 SUPPLEMENTS |
| | FBC-2007 EXISING BUILDING |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | |
| | |
| | 1. PLEASE INDICATE THE OCCUPANCY ON THE PLANS. SECTION |
| | 106.3.5.1.1(2). |
| | |
| | 2. A DESIGN PROFESSIONAL OR ON OWNER MUST ELECT ONE OR |
| | A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THE EXISTING BUILDING |
| | CODE. SECTION 401.4. PLEASE INDICATE ON PLANS. |
| | |
| | 3. MORE INFORMATION IS REQUIRED ON THE LAUNDRY ROOM. |
| | SECTION 106.1.2. IS THE LAUNDRY ROOM FOR UNIT ONE ONLY? |
| | IF NOT A FLOOR DRAIN IS REQUIRED PER SECTION 412.4 OF |
| | THE PLUMBING CODE. IF ONLY FOR APT. #1 THE A WASH |
| | MACHINE CONNECTION IS ALSO REQUIRED FOR APT. #2. TABLE |
| | 403.1. PLEASE CLARIFY. |
| | |
| | 4. SHT PL-1 THE SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS. IN APT #1 THE VENT CONNECTIONS FOR |
| | THE TUB BATH BETWEEN THE W/C AND THE TUB AND BY THE W/C |
| | IN THE SHOWER ARE DRY HORIZONTAL VENTS WHICH ARE |
| | PROHIBITED. SECTIONS 905.3 & 905.4. -- IN APT #2 THE |
| | TUB IS NOT VENTED AS INDICATED. SECTION 901.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |