2009-08-24 10:01:422007 FBC W/2009 REVISIONS
 ADDITION
  
 1) THE MECHANICAL PLANS SPECIFY A PACKAGE UNIT ON SHEET
 6.1. THE MANUFACTURER'S SPECS. THAT WERE SUBMITTED ARE
 FOR A RHEEM SPLIT SYSTEM. PLEASE CORRECT.
  
 2) PROVIDE THE UNIT SPECIFICATIONS ON THE MECHANICAL
 PLANS.
  
 3) SUBMIT HEATING AND COOLING LOAD SIZING CALCULATIONS
 AS REQUIRED BY FBCR M1401.3
  
 4) THE PLANS SPECIFY A TOTAL AIR SUPPLY OF 350 CFM AND
 A 2 TON SYSTEM. THE SYSTEM APPEARS TO BE OVER-SIZED.
 PLEASE REVISE.
  
 5) SPECIFY THE CAPACITY OF THE NEW BATH EXHAUST. ALSO
 NOTE THAT THE BATHROOM EXHAUST SHALL DISCHARGE DIRECTLY
 TO THE EXTERIOR OF THE BUILDING. SEE FBCR M1507.2 AND
 M1507.3.
  