Plan Review Notes
Plan Review Notes For Permit 09080416
Permit Number 09080416
Review Stop G
Sequence Number 1
Notes
Date Text
2009-08-18 10:57:14PASSED/PROVISO:
  
 CONTRACTOR INDICATED 4 PSI DELIVERY PRESSURE, BUT
 PRESSURE VERIFIED IN THE FIELD AS 1/2 PSI. MINIMUM 1/2
 ID COPPER REQUIRED FOR PIPING UPSTREAM OF FIRST TEE.
 REGULATOR NOT REQUIRED AT COOKTOP.
  
  