| Plan Review Notes For Permit 09080374 |
| Permit Number |
09080374 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-27 06:45:16 | ***APPROVED*** | | | | | | 1) PLANS STAMPED WITH FOLLOWING REQUIREMENTS: | | | | | | A) FIRE ALARM TO BE UL CERTIFICATED FOR CENTRAL STATION | | | SERVICE. | | | B) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE. | | | C) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM WHEN ACTIVATED. |
|