2009-10-16 09:00:48** PROVISO **
  
 ** REVISE PLANS BEFORE ROUGH INSPECTION. REVISED PLANS
 WILL BE REQUIRED TO BE REVIEWED BY THIS OFFICE, STAMPED
 AND ON-SITE FOR FIRST ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: COMPLIANCE FOR CHAPTER 13 FOR NEW CONTROLS
 MEETING PRESCRIPTIVE REQUIREMENTS MUST BE MET. BASED ON
 REVISED PLANS THERE IS A NEW TIME CLOCK BEING ADDED
 WHICH IS OK HOWEVER ANY OVER RIDE CONTROLS SHALL
 AUTOMATICALLY SHUT OFF LIGHTING IN THE MAXIMUM TIMED
 PERMITTED BY THE FBC.
 AS THE SYMBOL LEGEND INDICATES THE OVER RIDES AS
 STANDARD SINGLE POLE SWITCHES, THIS WOULD NOT MEET
 CODE. BASED ON THE PLANS AN OCCUPANT COULD OVER RIDE
 TIME CLOCK, LEAVE THE BUILDING AND LIGHTING WOULD STAY
 ON INDEFINITELY.
 PLEASE ALSO SEE SEPARATE SPACES SUCH AS ANY OFFICE OR
 SPACE WITH FLOOR TO CEILING HEIGHT PARTITIONS. SEPARATE
 SPACE REQUIREMENTS HAVE BEEN REQUIRED IN THE LAST 8
 CODE REVISIONS/ADOPTIONS.
 SEE TELLER AREA FOR NEW DEVICE BEING INSTALLED. BASED
 ON SYMBOL LEGEND THIS IS A SINGLE POLE SWITCH WHICH
 WOULD LEAVE LIGHTS ON.
 PLEASE SEE 13-415.AB.1
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  