| 2009-09-17 19:23:57 | ** DENIED 2ND REVIEW ** |
| | |
| | ** SAME NOTES FROM PREVIOUS REVIEW |
| | |
| | |
| | 1) NOTE: PLEASE PROVIDE LIGHTING CONTROLS MEETING |
| | MINIMUM PRESCRIPTIVE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE CHAPTER 13. 13-415.AB.1.1,.1.2 AND .1.3. |
| | ONLY NEW LIGHTING CONTROLS BEING INSTALLED ARE REQUIRED |
| | TO MEET PRESCRIPTIVE. |
| | PLANS INDICATE NEW SINGLE POLE SWITCH BANK HOWEVER THIS |
| | IS A TENANT SPACE IN A BUILDING GREATER THAN 5K SQ FT. |
| | |
| | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS MEETING FBC 13-415.AB.5, 13-415.B.1. MUST |
| | SHOW THAT THE NEW LIGHTING BEING ADDED TO OTHER |
| | EXISTING LIGHTING DOES NOT EXCEED MAXIMUM ALLOWANCES AS |
| | STATED IN SPACES. |
| | ** PLEASE CALL TO GO OVER ON HOW TO SHOW CODE |
| | COMPLIANCE. PLEASE SEE CODE SECTIONS AS NOTED. |
| | |
| | 3) NOTE: PLANS STATE THE 2008 NFPA-70 ( NEC) HOWEVER |
| | THE 2008 NEC HAS NOT YET BEEN ADOPTED BY THE STATE. IF |
| | THIS WAS THE ONLY ITEM PLANS WOULD HAVE BEEN REDLINED |
| | FOR THIS. |
| | THERE IS NOT NEED TO REPRINT COVER SHEETS TO MAKE THESE |
| | CORRECTIONS. |
| | |
| | 4) NOTE: PLANS DO NOT SHOW ANY INFORMATION FOR ADA |
| | COMPLIANCE FOR HORN, HORN/STROBE DEVICES. |
| | PLEASE SEE 11-4.28, .1,.2 AND .3. |
| | |
| | |
| | ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY |
| | COMMENTS. |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |