| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THESE COMMENTS ARE FROM SHEET E1.0 |
| | |
| | 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2007 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| | FBC AS AMENDED. |
| | |
| | 2} 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED BY |
| | CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE |
| | CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL |
| | LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE |
| | READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE |
| | THE CONTROLLED LIGHTING. A. A CONTROL DEVICE SHALL BE |
| | INSTALLED THAT AUTOMATICALLY TURNS LIGHTING OFF WITHIN |
| | 30 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, EXCEPT |
| | SPACES WITH MULTI-SCENE CONTROL, IN THE FOLLOWING: |
| | 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| | LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| | CLASSROOMS) |
| | 2. CONFERENCE/MEETING ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | |
| | 3} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE |
| | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A |
| | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD |
| | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR |
| | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING |
| | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN |
| | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| | POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION13-415.B.1***THIS CAN BE DEMONSTRATED ON THE |
| | PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN |
| | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. |
| | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE |
| | WITH THE ONES IN THE CALCULATIONS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |