Plan Review Notes
Plan Review Notes For Permit 09080335
Permit Number 09080335
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-27 07:08:03222 LAKEVIEW AVENUE, SUITE 100
 PERMIT # 09080335 AND 09080337
  
 1. SEVERAL ERRORS EXIST IN CODE DATA BOX ON PAGE A.0.0
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. DEBIRS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 5. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
 6. NO FIRE ALARM INITIATING OR SIGNALING APPLIANCES
 LOCATED ON THE DRAWINGS.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX