| Plan Review Notes For Permit 09080335 |
| Permit Number |
09080335 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-27 07:08:03 | 222 LAKEVIEW AVENUE, SUITE 100 | | | PERMIT # 09080335 AND 09080337 | | | | | | 1. SEVERAL ERRORS EXIST IN CODE DATA BOX ON PAGE A.0.0 | | | | | | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 3. DEBIRS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODEL. | | | | | | 5. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRIC CODE. | | | | | | 6. NO FIRE ALARM INITIATING OR SIGNALING APPLIANCES | | | LOCATED ON THE DRAWINGS. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | SPRINKLER SYSTEM REMODEL. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|