2009-08-20 08:26:51BUILDING PLAN REVIEW
 PERMIT: 09080335
 ADD: 222 LAKEVIEW AV# 100
 CONT: MENEMSHA DEVELOPMENT
 TEL: (718)337-9012X247
 FL BLD CODE= 2074 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 20/2009
 1ST REVIEW
 ACTION: DENIED
  
 1)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) SHEET A.0 / CODE DATA & CORRECTIONS;
 2A) LOCATION OF PROJECT, WEST PALM BEACH, FL
  
 2B) CONSTRUCTION TYPE: TYPE I-A NOT A V-B
  
 2C) BUILDING HEIGHT NOT A MULTI-STORY BUT HIGHRISE
 SECTION 403
  
 2D) FIRE RESISTANCE RATINGARE LISTED FOR A V-B CORRECT
 TO A TYPE I-A
  
 3) SHEET A3.0
  
 3A) DETAIL# 4 INDICATES THE USE OF PLYWOOD BLOCKING
 BETWEEN STUDS. PLEASE REVIEW 603.3.1.1USE OF FIRE
 RETARDANT TREATED WOOD (11) BLOCKING.
  
 3B) DETAIL# 5 INDICATESTHE USE OF WOOD STUDS,
 603.1.1(1.1)
  
 4) SHEET A3.3 DETAILS 3&4 INDICATE THE USE OF 1/2"
 PLYWOOD PANEL LAMINATES PLEASE REVIEW 803.4.1, 803.4.2
 & 803.4.4.PLEASE PROVIDE COMPLIANCE WITH ONE OF THESE
 SECTIONS.
  
 5) ATM MACHINES INDICATE ON SHEET A1.0 COMMENT NUMBER
 42 ATM TO BE REMOVED AND OR RELOCATED, SHEET A1.1
 DETAIL 5G&H/ A3.1 INDICATES THE WIDTH OF THE MACHINE.
 BETWEEN DETAILS A&B IT INDICATES THE MACHINES ARE ADA
 COMPLIANT, PLEASE PROVIDE THE HEIGHT OF