Plan Review Notes
Plan Review Notes For Permit 09080328
Permit Number 09080328
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-25 12:12:25 
  
 PROVISO
  
 1} SMALL APPLIANCE CIRCUITS MISSING FROM PANEL
 SCHEDULE. MINIMUM 2@20 AMPS. 210.11(C)(1).
  
 2} BATH CIRCUITS ON SCHEDULE @ 15 AMPS. SEE
 210.11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  