Plan Review Notes
Plan Review Notes For Permit 09080284
Permit Number 09080284
Review Stop B
Sequence Number 1
Notes
Date Text
2009-08-13 13:43:42****PROVISO****
 REVISION REQUIRED BEFORE FIRST INSPECTION
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SUBMIT A FLOOR PLAN SHOWING WINDOW LOCATIONS AND
 SIZES.
  
 2. SUBMIT PRODUCT APPROVAL FOR THE IMPACT PROTECTION.
  
 3. APPLICATION DOES NOT INCLUDE A DOOR, BUT A DOOR
 PRODUCT APPROVAL WAS SUBMITTED. THE NOA IS BEING
 RETURNED TO CONTACTOR. IF YOU PROPOSE TO INSTALL DOORS,
 INCLUDE THE DOOR LOCATION(S) ON THE FLOOR PLAN AND
 SUBMIT THE PRODUCT APPROVAL WITH THE REVISION.
  
 4. FOR THE SHUTTERS, COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE, 2 SETS.
  
 5. CLEAR OPENINGS FOR BEDROOMS CANNOT BE REDUCED BY
 MORE THAN 5%, FBC R301.
  
  