| 2009-08-14 16:31:41 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | |
| | 1. SHT A-2 GREASE RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. THE FLOOR PLAN SHOWS 2 NEW FLOOR SINKS, 1 |
| | NEW FLOOR DRAIN AND ONE NEW SINK, BUT THE RISER DIAGRAM |
| | ONLY SHOWS THE FLOOR DRAIN. (SHT A3 SHOWS 3 FLOOR |
| | SINKS) PLEASE CORRELATE. PLEASE SHOW ALL NEW PIPING |
| | FROM THE CONNECTION TO THE EXISTING PIPING. SHOW ALL |
| | PIPE SIZES, TRAPS & VENTS. SECTIONS 106.3.5.1.3 & |
| | 701.1. |
| | |
| | 2. SUBMIT A WATER RISER DIAGRAM FOR ALL NEW WORK. SHOW |
| | ALL PIPE SIZES, VALVES & (WHERE REQUIRED) WATER HAMMER |
| | ARRESTORS. SECTIONS 106.3.5.1.3 & 601.1. |
| | |
| | 3. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE |
| | RECEPTORS. A FLOOR SINK OR HUB DRAIN IS REQUIRED PER |
| | SECTIONS 802.3 & 802.3.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |