| Plan Review Notes For Permit 09080250 |
| Permit Number |
09080250 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-09-16 15:04:07 | PROVISO: | | | 2007 FBC RESIDENTIAL R313.2.1 | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | | SHALL BE INTERCONNECTED AND HARD WIRED. | | | EXCEPTIONS: | | | INTERCONNECTION AND HARD-WIRING OF SMOKE ALARMS IN | | | EXISTING AREAS SHALL NOT BE REQUIRED WHERE THE | | | ALTERATIONS OR REPAIRS DO NOT RESULT IN THE REMOVAL OF | | | INTERIOR WALL OR CEILING FINISHES EXPOSING THE | | | STRUCTURE, UNLESS THERE IS AN ATTIC, CRAWL SPACE OR | | | BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS FOR HARD | | | WIRING AND INTERCONNECTION | | | | | | | | | SMOKE ALARMS LOCATED WITHIN 20' OF COOKING WILL NEED TO | | | BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE ALARMS AND | | | SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20 FT) | | | HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE | | | EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE | | | PHOTOELECTRIC TYPE. | | | | | | SERVICE OUTLETS FOR A/C EQUIPMENT.210.52(E), 210.8(3) | | | OUTDOORS 210.63 . | | | | | | REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), 21011.C.3 | | | 210.8A1 | | | | | | | | | |
|