| Plan Review Notes For Permit 09080249 |
| Permit Number |
09080249 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-14 16:14:34 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PROPOSED MEN'S BATHROOM REQUIRES MINIMUM 300 CFM | | | EXHAUST PER FBC-M TABLE 403.3. | | | | | | 2. PROVIDE WIND RESISTANT INSTALLATION DETAIL FOR | | | EXHAUST FANS AND CURBS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|