2009-08-14 16:14:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROPOSED MEN'S BATHROOM REQUIRES MINIMUM 300 CFM
 EXHAUST PER FBC-M TABLE 403.3.
  
 2. PROVIDE WIND RESISTANT INSTALLATION DETAIL FOR
 EXHAUST FANS AND CURBS.
  