Plan Review Notes
Plan Review Notes For Permit 09080249
Permit Number 09080249
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-08-24 12:50:30CONSTRUCT BLDG. ADDITION & REMODEL BATHROOMS ACCORDING
 TO PERMIT APPLICATION
 09080249
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. WRONG LIFE SAFETY CODE REFERENCED ON SHEET A-1.
 SHOULD READ NFPA 101, 2006 EDITION INSTEAD OF NFPA 101,
 2003 EDITION.
  
 4. ALL NEW ELECTRICAL WORK SHALL COMPLY WITH NFPA 70,
 THE NATIONAL ELECTRIC CODE.
  
 5. PLEASE INDICATE HOW THE NEW WROUGHT IRON FENCE AND
 IRON GATE IMPACTS EXITING FROM THE EXISTING PARISH HALL
 AND OTHER AREAS OF THE FACILITY.
  
 6. WHAT HARDWARE AND LOCKING DEVICES ARE PROPOSED FOR
 THE IRON GATE. IF THIS GATE IS USED TO REACH EXIT
 DISCHARGE, LOCKS IF PROVIDED SHALL NOT REQUIRE THE USE
 OF A KEY, TOOL, SPECIAL KNOWLDGE OF EFFORT FROM THE
 INSIDE. WHAT YPE OF DOOR KNOB ASSEMBLY WILL BE
 PROVIDED.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX