2009-08-27 11:44:37** PROVISO/REDLINED PLANS**
  
 *** THE FOLLOWING ARE SET FORTH AS A PROVISO. MAKE
 ADJUSTMENTS BEFORE INSPECTIONS
  
 1) NOTE: THE DEVICES SHOWN FOR LIGHTING CONTROLS IN
 BATHROOMS ARE NOTED AS *MOTION SENSORS*, THESE NEED TO
 BE DUAL TECHNOLOGY FOR SAFETY.
  
 2) NOTE: VIF EXISTING OR NEW FEEDERS TO RELOCATED PANEL
 *A*. 310.16
  
 3) NOTE: BATHROOMS WILL REQUIRE SOME SORT OF BATTERY
 BACK UP EMERGENCY LIGHT FIXTURE. FBC 1006.1.2, LS 101
 7.8,7.9.
  
 ** REDLINED PLANS AND WENT OVER COMMENTS WITH MR. JEFF
 LEWIS FROM ARCHITECTS OFFICE.
  