| 2009-09-30 10:17:51 | MECHANICAL PROVISO: |
| | M1602.4 BALANCED RETURN AIR. RESTRICTED RETURN AIR |
| | OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL |
| | ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE |
| | RETURN GRILL OR WHEN CEILING SPACES ARE USED AS RETURN |
| | PLENUMS AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE |
| | PORTION OF THE RETURN PLENUM TO ANOTHER. PROVISIONS |
| | SHALL BE MADE IN RESIDENTIAL BUILDINGS TO AVOID |
| | UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED |
| | BY RESTRICTED RETURN AIR. |
| | TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (4.6 MM) |
| | (OF GRILLE AREA) TO 100 CFM (0.05 M3/S) (OF SUPPLY AIR) |
| | FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING |
| | AN UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | SFP-100 |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |