| 2009-08-18 09:30:59 | RESIDENTIAL ELECTRICAL PLAN REVIEW |
| | PERMIT: 09080245 |
| | ADD: 822 30TH ST |
| | CONT: GLADES ROOFING |
| | TEL: (561)GLADES ROOFING CGC 954-593-5917 |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | |
| | 2) THE PERMIT APPLICATION UNDER DESCRIPTION OF WORK |
| | DOES NOT PROVIDE WHAT ELECTRICAL UPGRADES ARE GOING TO |
| | TAKE PLACE UNDER THIS PERMIT, PLEASE PROVIDE AN |
| | ITEMIZED LIST OF WHAT ELECTRICAL UPGRADES ARE TO OCCUR, |
| | THE ELECTRICAL LIST FROM 09080250 WOULD BE MUCH THE |
| | SAME FOR THIS PERMIT BUT NOT KNOWING WHAT WILL BE |
| | COVERED MAKES THE REVIEW SOMEWHAT MEANINGLESS. THESE |
| | COMMEENTS WILL BE GENERALLITIES UNTIL THE EXTENT OF |
| | WORK IS KNOWN. |
| | |
| | 106.1.1 ADMINISTRATIVE CODE, CONSTRUCTION DOCUMENTS |
| | SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 3) DISCREPANCY IN ELECTRICAL PANEL, CIRCUITS 12-13 ARE |
| | DESINATED FOR A/C COMPRESSOR WHEREAS THE PLANS INDICATE |
| | CIRCUITS 16& 18. |
| | |
| | 4) THE AIR COMPRESSORS ELECTRICAL SYSMBOL IS ACTUALLY |
| | DRAWN IN AS A 240 OULET NOT AS A REQUIRED DISCONNECT |
| | PLEASE CORRECT. |
| | 440.11 GENERAL. THE PROVISIONS OF PART II ARE INTENDED |
| | TO REQUIRE DISCONNECTING MEANS CAPABLE OF DISCONNECTING |
| | AIRCONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING |
| | MOTORCOMPRESSORS AND CONTROLLERS FROM THE CIRCUIT |
| | CONDUCTORS. PLEASE INDICATE A TRUE DISCONNECT. |
| | |
| | 5) FLOOR PLAN INDICATES A JUNCTION BOX IN THE KITCHEN, |
| | IS THIS TRUELY A JUNCTION BOX OR THE PANEL, IF A |
| | JUNCTION BOX WHERE IS THE PANEL? |
| | |
| | 6) THE OTHER ISSUE IS THE NEW 200 AMP DISCONNECT |
| | BREAKER, IS MISSING THE A/C RATING. 110.9 INTERRUPTING |
| | RATING. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING |
| | SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND THE |
| | CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE |
| | EQUIPMENT. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | OTHER THAN |
| | FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING AT |
| | NOMINAL CIRCUIT VOLTAGE SUFFICIENT FOR THE CURRENT THAT |
| | MUST BE INTERRUPTED . |
| | |
| | 7A) PANEL SCHEDULE REQUIRED PLEASE REVIEW: 408.4 |
| | CIRCUIT DICTIONARY. ALL CIRCUITS AND CIRCUIT |
| | MODIFICATINS SHALL BE LEGIBLY IDENTIFIED AS TO PURPOSE |
| | OR USE ON A CIRCUIT DIRECTORY LOCATED ON THE FACE OR |
| | INSIDE OF THE PANEL DOOR IN THE CASE OF A PANEL OARD, |
| | AND AT EACH SWITCH ON A SWITCHBOARD. NOTE IDENTIFY |
| | CIRCUITS BY ROOM NOT GENERAL LIGHTING OR RECEPTACLES. |
| | |
| | 7B) PANEL LOCATIONS NEED TO COMPLY WITH: 110.26 (1) |
| | DEPTH OF WORKING SPACE, (2) WIDTH OF WORKING SPACE & |
| | (3) HEIGTH OF WORKING SPACE. FOR BOTH PANEL LOCATIONS. |
| | THE DEDICATED ELECTRICAL SPACE MUST BE CLEAR OF ANY |
| | PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR EQUIPMENT |
| | FOREIGN TO THE ELECTRICAL INSTALLATION. PLUMBING, |
| | HEATING, VENTILATION, AND |
| | AIR-CONDITIONING PIPING, DUCTS, AND EQUIPMENT MUST BE |
| | INSTALLED OUTSIDE THE WIDTH AND DEPTH ZONE. |
| | |
| | 8) NOTE THE PANEL SCHEDULE DOES NOT INCLUDE THE RANGE( |
| | GAS), NOR DRYER SYMBOL INDICATING ELECTRICAL |
| | CONNECTIONS, IT IS UNKNOWN IF THESE APPLIANCES ARE |
| | ELECTRIC OR GAS, GAS RANGE WILL REQUIRE THE SMOKE |
| | ALARMS WILL NEED TO BE CARBON MONOXIDE DETECTORS ALSOFL |
| | S S 553.885. |
| | |
| | 9) THE BEDROOMS DO NOT INDICATE A SMOKE ALARM WITHIN |
| | THE UNIT NOR OUTSIDE OF THE BEDROOM PLEASE REVIEW FBC |
| | RESIDENTIAL 313.2(2) AND NFPA 72. |
| | |
| | 10) THE SMOKE ALARMS LOCATED WWITHIN 20' OF COOKING |
| | WILL NEED TO BE COMPLY WITH NFPA 72-11.8.3.5 (4) SMOKE |
| | ALARMS AND SMOKE DETECTORS INSTALLED WITHIN A 6.1 M (20 |
| | FT) HORIZONTAL PATH OF A COOKING APPLIANCE SHALL BE |
| | EQUIPPED WITH AN ALARM-SILENCING MEANS OR BE OF THE |
| | PHOTOELECTRIC TYPE. |
| | |
| | 11) UTILITY ROOM CIRCUIT IS NOT SHOWN ON PLANS |
| | REQUIRING A GFCI CIRCUIT. 210.8(C)(2) LAUNDRY BRANCH |
| | CIRCUIT. |
| | |
| | 12) BEDROOMS MISSING OUTLETS ON PLANS, PLEASE PROVIDE |
| | ARC FAULT OUTLET CIRCUIT PER 210.12(B) DWELLING UNIT |
| | BEDROOMS.210.52OUTLET SPACING. |
| | |
| | 13)LIGHTING NOT SHOWN ON PLANS SWITCH LOCATIONS |
| | 210.70.INTERIOR LOCATIONS |
| | |
| | 14) EXTERIOR EXIT LIGHTS NOT SHOWN NOR SWITCH LOCATIONS |
| | 210.70. |
| | |
| | 15) REQUIRED SERVICE OUTLETS FOR A/C |
| | EQUIPMENT.210.52(E), 210.8(3) OUTDOORS 210.63 . |
| | |
| | 16) THERMOSTATS ARE NOT SHOWN. |
| | |
| | 17) THE ELECTRIC RISER IS MISSING GROUND ROD LENGTH, |
| | 250.66 & TABLE 250.66. |
| | |
| | 18) LAUNDRY/ WASHER PLEASE REVIEW 210.52, 210.11C2 & |
| | 220.52.3 |
| | |
| | 19) MISSING EQUIPMENT GROUND BETWEEN MAIN AND PANEL |
| | 250.122 |
| | |
| | 20) REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D), |
| | 21011.C.3 210.8A1 |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |