| 2009-08-17 16:38:22 | RESIDENTIAL BUILDING PLAN REVIEW |
| | PERMIT: 09080245 |
| | ADD: 822 30TH ST |
| | CONT: GLADES ROOFING |
| | TEL: (561)GLADES ROOFING CGC 954-593-5917 |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | |
| | 2) PLANS DO NOT INDICATE ANY WIND DESIGN DRITERIA: |
| | |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 3) NEITHER THE PLANS NOR NOA INDICATE IF THESE WINDOWS |
| | ARE TO BE FASTEND THROUGH WOOD BUCKS, THE NOA SUBMITTED |
| | IS FOR FLANGED TYPE INSTALATION, THE CONCERN IS THE |
| | REQUIRED SEPERATION FROM GLASS TO SHUTTER IS 2 5/8 TO 3 |
| | 5/8 INCHES PLEASE INDICATE CODE COMPLIANCE FOR BOTH |
| | ISSUES. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 4) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE SQ. FT |
| | OF ROOF REPAIR AND WHAT PERCENTAGE.EXISTING BUILDING |
| | CODE. 611.1.1 NOT MORE THAN 25 PERCENT OF THE TOTAL |
| | ROOF AREA OR ROOF SECTION OF ANY EXISTING BUILDING OR |
| | STRUCTURE SHALL BE REPAIRED, REPLACED OR RECOVERED IN |
| | ANY 12 MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR |
| | ROOF SECTION CONFORMS TO REQUIREMENTS OF THIS CODE. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |