| Plan Review Notes For Permit 09080235 |
| Permit Number |
09080235 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-18 14:03:13 | 2007 FBC W/2009 REVISIONS | | | ADDITION OF COVERED PATIO | | | | | | DENIED BY BUILDING | | | | | | 1) THE PROJECT IS LOCATED IN EXPOSURE C, BASED ON | | | REVISED SECTIONS R301.2.1.4.2 AND R301.2.1.4.3. PLEASE | | | REVISED PLANS AND ENHANCED FASTENING CALCULATIONS FOR | | | THE GAF MODIFIED ROOF SYSTEM. | | | | | | 2) THE ROOF SHEATHING IS REQUIRED TO BE FASTENED WITH | | | 8D RING SHANK NAILS PER FBC R803.2.3.1. PLEASE REVISE | | | SECT. 1 ON A2. | | | | | | 3) THE STUCCO ON THE PAPER BACK LATH OVER THE 5/8" | | | PLYWOOD IS REQUIRED TO BE 7/8" THICK PER FBC R703.6.1 | | | AND ASTM C 926. PLEASE REVISE NOTE ON SECT. 2 ON A2. | | | | | | 4) THE ROOF UPLIFT PRESSURES ON SHEET A2 WILL NEED TO | | | BE REVISED FOR EXPOSURE C. FBC R301.2.1 | | | | | | 5) THE WORDING IN THE ENHANCED FASTENING IS MISLEADING. | | | IT STATES TO USE APPROVED SCREWS OR NAILS AND PLATES. | | | IN ORDER TO, ACHIEVE THE -75 PSF DESIGN PRESSURE SCREWS | | | AND PLATES ARE REQUIRED AND NOT NAILS. ALSO, WHICH OF | | | THE FASTENING OPTIONS IS BEING ENHANCED FOR THE | | | CORNERS. PROVIDE THE RAS 117 CALCULATIONS AS REQUIRED | | | BY LIMITATION NUMBER 7 OF THE NOA NO. 09-0224.01. | | | | | | 6) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON CONNECTORS | | | OR SPECIFY THE FLORIDA APPROVAL NUMBERS ON THE PLANS. | | | DCA RULE 9B-72. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|