Plan Review Notes
Plan Review Notes For Permit 09080235
Permit Number 09080235
Review Stop B
Sequence Number 1
Notes
Date Text
2009-08-18 14:03:132007 FBC W/2009 REVISIONS
 ADDITION OF COVERED PATIO
  
 DENIED BY BUILDING
  
 1) THE PROJECT IS LOCATED IN EXPOSURE C, BASED ON
 REVISED SECTIONS R301.2.1.4.2 AND R301.2.1.4.3. PLEASE
 REVISED PLANS AND ENHANCED FASTENING CALCULATIONS FOR
 THE GAF MODIFIED ROOF SYSTEM.
  
 2) THE ROOF SHEATHING IS REQUIRED TO BE FASTENED WITH
 8D RING SHANK NAILS PER FBC R803.2.3.1. PLEASE REVISE
 SECT. 1 ON A2.
  
 3) THE STUCCO ON THE PAPER BACK LATH OVER THE 5/8"
 PLYWOOD IS REQUIRED TO BE 7/8" THICK PER FBC R703.6.1
 AND ASTM C 926. PLEASE REVISE NOTE ON SECT. 2 ON A2.
  
 4) THE ROOF UPLIFT PRESSURES ON SHEET A2 WILL NEED TO
 BE REVISED FOR EXPOSURE C. FBC R301.2.1
  
 5) THE WORDING IN THE ENHANCED FASTENING IS MISLEADING.
 IT STATES TO USE APPROVED SCREWS OR NAILS AND PLATES.
 IN ORDER TO, ACHIEVE THE -75 PSF DESIGN PRESSURE SCREWS
 AND PLATES ARE REQUIRED AND NOT NAILS. ALSO, WHICH OF
 THE FASTENING OPTIONS IS BEING ENHANCED FOR THE
 CORNERS. PROVIDE THE RAS 117 CALCULATIONS AS REQUIRED
 BY LIMITATION NUMBER 7 OF THE NOA NO. 09-0224.01.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON CONNECTORS
 OR SPECIFY THE FLORIDA APPROVAL NUMBERS ON THE PLANS.
 DCA RULE 9B-72.
  
  