| 2009-12-21 09:58:24 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. **NOT ADDRESSED** THE PROPOSED SCOPE OF WORK SHOWS |
| | AN INCREASE IN THE CONDITIONED SPACE WITHIN THIS |
| | BUILDING. AN EXTENSION OR INCREASE IN CONDITIONED FLOOR |
| | AREA OF A BUILDING IS CONSIDERED AN ADDITION PER FBC-B |
| | 13-202. ADDITIONS TO EXISTING COMMERCIAL BUILDINGS ARE |
| | CONSIDERED NEW BUILDING CONSTRUCTION AND SHALL COMPLY |
| | WITH METHOD A OF SUBCHAPTER 13-4 OF THIS CODE AS |
| | ALLOWED IN SECTION 13-101.1.1. PROVIDE A METHOD A CODE |
| | COMPLIANCE FORM AND AN APTTACHED COOLING LOAD |
| | CALCULATION IN ACCORDANCE WITH THIS SECTION AND FBC-B |
| | 13-407.AB.1. |
| | |
| | 2. OK |
| | |
| | 3. **NEED ENERGY CALCULATIONS** AN AIR BARRIER IS |
| | REQUIRED BETWEEN THE CONDITIONED AND UNCONDITIONED |
| | SPACE AT THE BUILDING THERMAL ENVELOPE. A DROPPED T-BAR |
| | TYPE CEILING CAN NOT SERVE THIS PURPOSE. AIR BARRIERS |
| | SHALL BE IN ACCORDANCE WITH FBC-B 13-406.AB. THIS |
| | APPLIES TO EXTERIOR WALLS AND ROOF/CEILINGS. |
| | |
| | 4. OK |
| | NOTE: A TEST AND BALANCE REPORT WILL BE REQUIRED AT |
| | FINAL INSPECTION TO CONFIRM VENTILATION RATES IN |
| | ACCORDANCE WITH FBC-M 403.3.4. |
| | |
| | 5. OK |
| | |
| | 6. **NOT ADDRESSED** PAGE M-501 SHOWS CONDENSATE FROM |
| | NEW AHU DISCHARGING INTO FLOOR DRAIN. IS THIS FLOOR |
| | DRAIN PART OF A SANITARY SEWER SYSTEM? CONDENSATE SHALL |
| | NOT DISCHARGE INTO SANITARY SEWER SYSTEMS PER CITY |
| | ORDINANCE. CONDENSATE SHALL DISCHARGE OUTDOORS AT AN |
| | APPROVED LOCATION IN ACCORDANCE WITH FBC-M 307.2.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |