| 2009-08-22 11:07:43 | MECHANICAL PLAN REVIEW |
| | PERMIT: 09080208 |
| | ADD: 1112 FLORIDA AVE |
| | CONT: GEORGE FRAKER |
| | TEL: (561)502-4699 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | AUGUST 22/2009 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET M-1 UNDER THE MECH SPEC NOTES INDICATE THE |
| | INSTALATION OF A SPLIT SYSTEM WITH A 12 SEER VALUE. |
| | UNDER THE 2009 FBC CHAPTER 13, PLEASE REVIEW MINIMUM |
| | EFFICIENCIES FOR COOLING EQUIPMENT. TABLE |
| | 13-607.ABC.3.2A A MINIMUM SEER VALUE FOR AIR COOLED, |
| | AIR CONDITIONERS O 65.0K BTU OR LESS. PLEASE ALSO NOTE |
| | THE ENERGY FORM 1100A-08 INDICATES A 16.5 SEER UNIT AS |
| | WELL AS THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY |
| | CARD. PLEASE UPDATE PLANS TO THE CURRENT ENERGY |
| | EFFICIENCY AS STATED IN THE ENERGY CALCULATIONS. |
| | |
| | 2) SHEET M-1 SECOND LEVEL THE BRANCH SUPPLY DUCT FROM |
| | THE AIR HANDLIER TO THE DISTRUBUTION BOX LOCATED ABOVE |
| | BEDROOM# 1 DOES NOT INDICATE A DUCT SIZE.M1601.01 DUCT |
| | DESIGN. |
| | |
| | 3) PLANS FAIL TO INDICATE COMPLIANCE WITH: |
| | 3A) M1411.3 CONDENSATE DISPOSAL |
| | B) M14.11.3.1 AUXILIARY AND SECONDARY DRAIN SYSTEMS. |
| | C) M14.11.3.2 DRAIN PIPE MATERIALSS AND SIZES |
| | D) M1411.4 AUXILIARY DRAIN PAN. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | SFP-100 |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |