| 2009-08-13 08:06:44 | BUILDING PLAN REVIEW |
| | PERMIT: 09080208 |
| | ADD: 1112 FLORIDA AVE |
| | CONT: GEORGE FRAKER |
| | TEL: (561)502-4699 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | AUGUST 13/2009 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | RESIDENTIAL BUILDING WITH 2009 SUPPLEMENTS. PLEASE |
| | UPDATE PLANS TO THE CURRENT CODE EDITION AND |
| | REQUIREMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. PLEASE UPDATE |
| | PLANS TO THE CURRENT CODE EDITION AND REQUIREMENTS. |
| | |
| | 2A) SHEET A-4 PLEASE REVIEW FLOOR ASSEMBLIES BENEATH |
| | 1ST FLOOR AND THE 2ND FLOOR/ CEILING ASSEMBLY, PLEASE |
| | CONFORM TO SECTIONR317.1. R317.1 TWO-FAMILY DWELLINGS. |
| | DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE |
| | SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR |
| | ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR |
| | FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 119. FIRE-RESISTANCE-RATED FLOOR-CEILING AND |
| | WALL ASSEMBLIES SHALL EXTEND TO AND BE TIGHT AGAINST |
| | THE EXTERIOR WALL, AND WALL ASSEMBLIES SHALL EXTEND TO |
| | THE UNDERSIDE OF THE ROOF SHEATHING. |
| | |
| | 2B) PLEASE ALSO PROVIDE FIRE PENETRATION PROTECTION IN |
| | THE TENANT SEPERATION WALL PERR317.3.1 THROUGH |
| | PENETRATIONS. THROUGH PENETRATIONS OF |
| | FIRE-RESISTANCE-RATED WALL OR FLOOR ASSEMBLIES SHALL |
| | COMPLY WITH SECTION R317.3.1.1 OR R317.3.1.2. |
| | |
| | EXCEPTION: WHERE THE PENETRATING ITEMS ARE STEEL, |
| | FERROUS OR COPPER PIPES, TUBES OR CONDUITS, THE ANNULAR |
| | SPACE SHALL BE PROTECTED AS FOLLOWS: |
| | |
| | 1. IN CONCRETE OR MASONRY WALL OR FLOOR ASSEMBLIES |
| | WHERE THE PENETRATING ITEM IS A MAXIMUM 6 INCHES (152 |
| | MM) NOMINAL DIAMETER AND THE AREA OF THE OPENING |
| | THROUGH THE WALL DOES NOT EXCEED 144 SQUARE INCHES (92 |
| | 900 MM2), CONCRETE, GROUT OR MORTAR IS PERMITTED WHERE |
| | INSTALLED TO THE FULL THICKNESS OF THE WALL OR FLOOR |
| | ASSEMBLY OR THE THICKNESS REQUIRED TO MAINTAIN THE |
| | FIRE-RESISTANCE RATING. |
| | |
| | 2. THE MATERIAL USED TO FILL THE ANNULAR SPACE SHALL |
| | PREVENT THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT |
| | TO IGNITE COTTON WASTE WHERE SUBJECTED TO ASTM E 119 |
| | TIME TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER (3 |
| | PA) AT THE LOCATION OF THE PENETRATION FOR THE TIME |
| | PERIOD EQUIVALENT TO THE FIRE RESISTANCE RATING OF THE |
| | CONSTRUCTION PENETRATED. |
| | |
| | 2C) PLEASE PROVIDE INFORMATION ON THE 1 HR RATING |
| | BEHIND THE ELECTRICAL PANELS BACK TO BACK INTHE TENANT |
| | SEPERATION WALL. R-317.1. |
| | |
| | 2D) INTERIOR TYPICAL BEARING WALL DETAIL INDICATES STEM |
| | WALL CONSTRUCTION A PT SILL PLATE AND WHAT APPEARS TO |
| | BE CONCRETE BETWEEN FLOOR JOIST PLEASE INDICATE TYPE OF |
| | MATERIAL TO BE PLACED IN THIS AREA, 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 2E ) EXTERIOR BEARING WALL AT THE TOP OF THE SECOND |
| | FLOOR TRUSSES, MISSING A BOTTOM PLATE WHICH ALSO ACTS |
| | AS A FIRE STOP BETWEEN VERTICAL AND HORIZONTAL AREAS. |
| | R602.1.2. |
| | |
| | 3) SHEET A2-4 INDICATE NEW PORCHES BUT NONE OF THE |
| | DETAILS PROVIDED INDICATE THE TYPES OF HOLD DOWN |
| | DEVICES NOR LOADS TO BE RESTRAINED. PART OF THE MAIN |
| | WIND RESISTANCE SYSTEM, FOUNDATION THROUGH ROOF |
| | FRAMING. R601.2 CONTINIOUS LOAD PATH FROM FOUNDATION, |
| | WALLS TO ROOF FRAMING. |
| | |
| | 4) PLEASE CIRCLE TYPE OF TILE ATTACHMENT IN THE ROOFING |
| | NOA 05-0921.02 .THE LISTING IN THE NOA ARE FOOT -LBS |
| | NOT PSF. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |