2009-09-16 19:07:56** PROVISO/REDLINED PLANS**
  
 1) NOTE: PLANS CONTAIN A NEW A/C SYSTEM PER MECHANICAL
 COMMENTS WHICH WAS NOT ON EITHER OF THE TWO PREVIOUS
 REVIEWED PLANS.
 NEW ELECTRICAL PLANS DO NOT INDICATE THE REQUIRED
 ELECTRICAL TO AHU. NEEDS DISCONNECT MEETING 440.11,12,
 110.26.
  
 2) NOTE: THE OVER CURRENT PROTECTION INDICATED FOR
 EXISTING AIR HANDLER UNITS WITH 5KW HEAT IS SHOWN TOO
 HIGH. HEAT STRIPS ARE SHOWN AT 5KW> PLEASE SEE 424.3B
 AS MINIMUM OCP IS 125%, HOWEVER PLEASE SEE 422.11E3 AS
 THE MAXIMUM OCP IS 150% OR MANUFACTURES NAMEPLATE. THE
 60AMP AS SHOWN APPEARS TOO HIGH AND IS A POSSIBLE
 FIRE/LIFE SAFETY HAZARD. THIS WAS IN PREVIOUS NOTES.
 PLEASE VIF AND ADJUST BREAKERS AS NEEDED.
  
 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES. PLEASE SUBMIT BEFORE
 FINAL ELECTRICAL INSPECTION. ANY OTHER CHANGES ARE
 REQUIRED BEFORE ROUGH.
 AS CIRCUITING IS NOT SHOWN, PLANS ARE REDLINED FOR
 EMERGENCY AND EXIT LIGHTS TO MEET 700.12F AS TYPICAL.
 ALL MUST BE CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT
 IN ANY ONE AREA.
  
 4) NOTED *** ONLY THE FIXTURE OUTSIDE SOUTH DOOR NEEDS
 TO BE ADDED AS BATTERY BACK UP OF SOME KIND TO MEET
 NFPA-101 7.8.1.3,7.9.1.2,.2.2.
  
 5) NOTED *** ANY REVISIONS BY OTHER TRADES SUCH AS THE
 SIZING OF THE A/C SYSTEM MAY AFFECT ELECTRICAL PLANS.
 ELECTRICAL REVIEW IS BASED ON SYSTEM SHOWN ON PLANS AT
 THIS TIME. IT IS KNOWN THERE MAY BE CODE COMMENTS WITH
 RESPECT TO THE SIZE OF THE A/C SYSTEM AS SUBMITTED AND
 SHOWN.
  
 6) NOTED *** SERVICE RISER/METER IS SHOWN AS IT EXISTS
 ON PLANS AND AT LOCATION. ONLY MOVING MAIN OUTSIDE TO
 GROUP MAINS FOR SERVICES TO MEET 230.72. ADDITIONAL
 SERVICE IS NOT GRANTED PER 230.2. HOWEVER AS IT IS
 EXISTING SIGNAGE FOR ALL SERVICES AND MAIN LOCATIONS
 SHALL BE INSTALLED AT THIS SERVICE.
 ** ALL OTHER MAINS AND SERVICES ON BUILDING SHALL BE
 LABELED PER 230.2E. VERIFY IN FIELD. ALL SERVICES
 INCLUDING HOUSE SERVICE IS THE RESPONSIBILITY OF
 BUILDING OWNER.
  
 ** AS STATED ON ALL REVIEWS PREVIOUSLY, PLEASE CALL TO
 GO OVER ANY QUESTIONS.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  