| 2009-09-16 19:07:56 | ** PROVISO/REDLINED PLANS** |
| | |
| | 1) NOTE: PLANS CONTAIN A NEW A/C SYSTEM PER MECHANICAL |
| | COMMENTS WHICH WAS NOT ON EITHER OF THE TWO PREVIOUS |
| | REVIEWED PLANS. |
| | NEW ELECTRICAL PLANS DO NOT INDICATE THE REQUIRED |
| | ELECTRICAL TO AHU. NEEDS DISCONNECT MEETING 440.11,12, |
| | 110.26. |
| | |
| | 2) NOTE: THE OVER CURRENT PROTECTION INDICATED FOR |
| | EXISTING AIR HANDLER UNITS WITH 5KW HEAT IS SHOWN TOO |
| | HIGH. HEAT STRIPS ARE SHOWN AT 5KW> PLEASE SEE 424.3B |
| | AS MINIMUM OCP IS 125%, HOWEVER PLEASE SEE 422.11E3 AS |
| | THE MAXIMUM OCP IS 150% OR MANUFACTURES NAMEPLATE. THE |
| | 60AMP AS SHOWN APPEARS TOO HIGH AND IS A POSSIBLE |
| | FIRE/LIFE SAFETY HAZARD. THIS WAS IN PREVIOUS NOTES. |
| | PLEASE VIF AND ADJUST BREAKERS AS NEEDED. |
| | |
| | 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH PANEL SCHEDULES. PLEASE SUBMIT BEFORE |
| | FINAL ELECTRICAL INSPECTION. ANY OTHER CHANGES ARE |
| | REQUIRED BEFORE ROUGH. |
| | AS CIRCUITING IS NOT SHOWN, PLANS ARE REDLINED FOR |
| | EMERGENCY AND EXIT LIGHTS TO MEET 700.12F AS TYPICAL. |
| | ALL MUST BE CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT |
| | IN ANY ONE AREA. |
| | |
| | 4) NOTED *** ONLY THE FIXTURE OUTSIDE SOUTH DOOR NEEDS |
| | TO BE ADDED AS BATTERY BACK UP OF SOME KIND TO MEET |
| | NFPA-101 7.8.1.3,7.9.1.2,.2.2. |
| | |
| | 5) NOTED *** ANY REVISIONS BY OTHER TRADES SUCH AS THE |
| | SIZING OF THE A/C SYSTEM MAY AFFECT ELECTRICAL PLANS. |
| | ELECTRICAL REVIEW IS BASED ON SYSTEM SHOWN ON PLANS AT |
| | THIS TIME. IT IS KNOWN THERE MAY BE CODE COMMENTS WITH |
| | RESPECT TO THE SIZE OF THE A/C SYSTEM AS SUBMITTED AND |
| | SHOWN. |
| | |
| | 6) NOTED *** SERVICE RISER/METER IS SHOWN AS IT EXISTS |
| | ON PLANS AND AT LOCATION. ONLY MOVING MAIN OUTSIDE TO |
| | GROUP MAINS FOR SERVICES TO MEET 230.72. ADDITIONAL |
| | SERVICE IS NOT GRANTED PER 230.2. HOWEVER AS IT IS |
| | EXISTING SIGNAGE FOR ALL SERVICES AND MAIN LOCATIONS |
| | SHALL BE INSTALLED AT THIS SERVICE. |
| | ** ALL OTHER MAINS AND SERVICES ON BUILDING SHALL BE |
| | LABELED PER 230.2E. VERIFY IN FIELD. ALL SERVICES |
| | INCLUDING HOUSE SERVICE IS THE RESPONSIBILITY OF |
| | BUILDING OWNER. |
| | |
| | ** AS STATED ON ALL REVIEWS PREVIOUSLY, PLEASE CALL TO |
| | GO OVER ANY QUESTIONS. |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |