Plan Review Notes
Plan Review Notes For Permit 09080203
Permit Number 09080203
Review Stop E
Sequence Number 2
Notes
Date Text
2009-08-21 15:32:14 
  
  
 ** DENIED 2ND REVIEW **
  
 ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING. SOME NEW NOTES BASED ON REVISED PLANS NOW
 SHOWING INFORMATION NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE NOW SUBMITTED PANEL SCHEDULES.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF EXIT
 AND EMERGENCY LIGHTS AS NOTED ON PREVIOUS REVIEW.
 408.4
 240.4,310.16 ETC SEE NOTES BELOW.
  
 2) NOTE: PANEL SCHEDULES NOW SUBMITTED ALONG WITH LOAD
 CALCULATIONS INDICATE 2-POLE 60AMP BREAKERS ON AHU*S
 HOWEVER THE HEAT LOADS ON HAU ARE SHOWN AS 5KW EACH.
 PLEASE SEE 424.3B AND 422.11E AS MINIMUM OVER CURRENT
 PROTECTION WOULD BE 125% HOWEVER MAXIMUM OCP WOULD BE
 150%/ MANUFACTURES NAMEPLATE.
 IT IS NOT POSSIBLE TO HAVE 60AMP OCP ON 5KW AIR HANDLER
 UNITS. IF THE UNITS ARE ACTUALLY 10KW, PLEASE ADJUST
 LOAD CALCULATIONS.
 220,220.56 ETC
  
 3) NOTE: PLEASE WHO NEW OR EXISTING SIGN CIRCUIT AND
 MINIMUM LOAD OF 1200 VA PER 600.5 AS NOTED ON PREVIOUS
 REVIEW. PLANS NOW CONTAIN A NOTE WHICH MENTIONS * NO
 ELECTRICAL SIGNAGE* HOWEVER THE MINIMUM REQUIRED BY THE
 NEC IS THAT A SIGN CIRCUIT BE PROVIDED EVEN IF THE
 TENANT DOES NOT INSTALL AN ELECTRICAL SIGN. PLEASE SEE
 THE FOLLOWING COMMENTARY FROM THE NEC FROM SECTION
 600.5. THIS IS PASTED DIRECTLY FROM THE NEC HANDBOOK.
  
 **ELECTRIC SIGNS AND OUTLINE LIGHTING TO ATTRACT THE
 ATTENTION OF CONSUMERS ARE USED EXTENSIVELY BY
 COMMERCIAL ENTERPRISES. THE NEED FOR AN ACCESSIBLE
 PROVISION TO FACILITATE THE CONNECTION OF AN ELECTRIC
 SIGN AT A COMMERCIAL BUILDING IS COVERED BY 600.5(A). A
 20-AMPERE OUTLET ON A CIRCUIT DEDICATED TO THE PURPOSE
 OF SUPPLYING AN ELECTRIC SIGN(S) IS REQUIRED TO BE
 INSTALLED AT THE ENTRANCE TO SINGLE-OCCUPANT COMMERCIAL
 BUILDINGS AND AT THE ENTRANCE TO EACH OCCUPANCY OF
 MULTIPLE-OCCUPANT COMMERCIAL BUILDINGS (E.G., SHOPPING
 MALLS). THIS REQUIREMENT IS NOT CONTINGENT ON WHETHER
 AN ELECTRIC SIGN WILL BE INSTALLED AT THE TIME AN
 OCCUPANT MOVES INTO A COMMERCIAL SPACE, SINCE IT IS NOT
 UNCOMMON FOR AN ELECTRIC SIGN TO BE INSTALLED AFTER THE
 SPACE IS OCCUPIED OR WHEN A NEW OCCUPANT MOVES INTO AN
 EXISTING SPACE. FOR BRANCH CIRCUIT, FEEDER AND SERVICE
 CALCULATIONS, A MINIMUM LOAD OF 1200 VA PER 20-AMPERE
 SIGN BRANCH CIRCUIT IS REQUIRED TO BE ADDED. DUE TO THE
 NATURE OF THEIR USE, ELECTRIC SIGNS ARE CONSIDERED TO
 BE CONTINUOUS LOADS, AND AS SUCH THE CONDUCTORS AND
 OVERCURRENT DEVICES SUPPLYING SIGN LOADS HAVE TO BE
 ADJUSTED IN SIZE ACCORDINGLY.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS AS PREVIOUS REVIEW NOTES PER 13-415.AB.5,
 13-415.400.B.0.4, 13-415.B, 13-415.B.1.
 NO INFORMATION SUBMITTED. PLEASE KEEP IN MIND THIS IS
 PRESCRIPTIVE ONLY. IF USING FLA COM FOR CALCULATIONS,
 PLEASE KNOW THAT ONLY THE LIGHTING NEED BE PLACED INTO
 CALCULATION UNLESS OTHER PRESCRIPTIVE ITEMS ARE BEING
 CHANGED OR INSTALLED. IE: A/C EQUIPMENT. SEE MECHANICAL
 NOTES.
 *** AS STATED ON PREVIOUS REVIEW PLEASE CALL TO GO
 OVER.
  
 5) NOTE: OCCUPANT LOAD ON ELECTRICAL PLANS STILL STATE
 60, PLEASE BE SURE TO REVISE FOR FIRE MARSHAL REVIEW
 NOTES ALONG WITH BUILDING REVIEW NOTES.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 LIGHTING CONTROLS IN SPACE. 13-415.AB.1.1,.1.2 AND
 .1.3.
 PLEASE SEE PLANS WHICH DO INDICATE SOME OCCUPANCY
 SENSORS HOWEVER IT IS NOT CLEAR WHAT THE SYMBOL AND
 DEVICE IS FOR * S MT*.
  
  
 7) NOTE: PLANS NOW NOTE A * OPEN/CLOSE DOOR CARD*
 HOWEVER NO INFORMATION WAS PROVIDED ON PLANS FOR
 CHAPTER 7 OF THE LIFE SAFETY CODE NFPA-101. PLEASE SEE
 SECTIONS. 7.2.1.5, 7.2.1.6.2 FOR ACCESS CONTROLS. ALL
 ACCESS CONTROLS SHALL BE UNDER SEPARATE LOW VOLTAGE
 PERMITS AND PLANS.
  
  
 8) NOTE: PLEASE SHOW LOAD CALCULATIONS PER NEC 220.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
 SEE NOTES ABOVE FOR ITEMS SUCH AS SIGN CIRCUIT, A/C
 UNITS, ETC
 SEE 220.12,220.14,220.42,220.44, 220.56 ETC.
 215.3,.230.42 FOR CONTINUOUS LOADS.
  
 9) NOTE: PLEASE SEE 210.63, 210.8B, AS NEW OR EXISTING
 GFI IS REQUIRED FOR CONDENSING UNITS OUTSIDE. IF THIS
 WAS THE ONLY ITEM PLANS WOULD HAVE BEEN REDLINED.
  
 10) NOTE: PLEASE EXPLAIN CONDUCTORS ON RISER FROM METER
 TO MAIN AND MAIN TO PANEL. SHOWS 3-3/0 AND 1-#1. THIS
 IS A SINGLE PHASE SERVICE. ONLY THE PHASE CONDUCTORS
 AND NEUTRAL IS PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT. 250.24,250.6. AS THE NEC REQUIRES THE
 NEUTRAL (GROUNDED CONDUCTOR) TO BE BONDED AT THE FIRST
 MEANS OF DISCONNECT IF AN EQUIPMENT GROUNDING CONDUCTOR
 IS INSTALLED THEN THIS WOULD PARALLEL THE NEUTRAL AND
 CREATE OBJECTIONABLE CURRENTS.
 ONLY AFTER THE FIRST MEANS OF DISCONNECT IS THE
 EQUIPMENT GROUNDING CONDUCTOR REQUIRED. PLEASE SEE
 250.122 FOR SIZING. RISER SHOWS #1, HOWEVER SEE
 SECTION.
 ** PLEASE SEE 250.66 FOR ANY NEW GROUNDING ELECTRODE
 CONDUCTOR.
 ** PLANS DO NOT SHOW MAIN DISCONNECT OUTSIDE. SIGNAGE
 WILL BE REQUIRED PER 230.2E.
  
 ** CALLED ELECTRICAL CONTRACTOR FOR MEETING SOME TIME
 THE FOLLOWING WEEK TO GO OVER PLANS/COMMENTS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  