2009-08-25 18:09:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART
 OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED MECHANICAL
 VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL , THE INTENT OF THE
 RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS
 SHALL BE COMPLIED WITH FOR THE NEW OCCUPANCY IN
 ACCORDANCE WITH FBC-EB 909.1. NO INFORMATION WAS
 PROVIDED REGARDING THE EXISTING AIR CONDITIONING SYSTEM
 OR THE VENTILATION RATES WHICH ARE BEING PROVIDED.
 DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF FBC-M
 403.3 OR 403.4 FOR THE NEW OCCUPANCY.
  
 NOTE: A TEST AND BALANCE REPORT WILL BE REQUIRED AT
 TIME OF INSPECTION (PRIOR TO C.O.) TO VERIFY
 VENTILATION RATES IN ACCORDANCE WITH FBC-M 403.3.4.
  