Plan Review Notes
Plan Review Notes For Permit 09080203
Permit Number 09080203
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-08-12 14:40:35*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. ON SHEET A-1, IT IS STATED THAT THE OCCUPANCY SPACE
 IS AN EXISTING ASSEMBLY; BE ADVISED THAT SINCE THIS A
 CHANGE OF OCCUPANCY FROM THAT OF MERCANTILE, THIS
 TENANT SPACE SHALL BE A NEW ASSEMBLY AS PER NFPA 101.
  
 4. PLEASE EXPLAIN THE OCCUPANT LOAD FACTOR OF 50 GROSS
 USED TO DERIVE AN OCCUPANT LOAD OF 60 PERSONS. BE
 ADVISED, AS PER 12.3.5.1 OF NFPA 101, WHERE THE
 OCCUPANT LOAD EXCEEDS 100, THE ASSEMBLY OCCUPANCY SHALL
 BE PROTECTED THROUGHOUT BY AN APPROVED SUPEWRVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 5. PROVIDE OCCUPANT LOAD FOR THE WAITING AREA.
  
 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICIATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW