| 2009-08-09 09:26:48 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLANS SPECIFICALLY STATE WORK TO BE DONE TO A |
| | 2006 FLORIDA BUILDING AS WELL AS STATING THE 2007 |
| | FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS. SEE NOTE |
| | #4 ON PLANS. |
| | AS OF MARCH 1ST, 2009 THE STATE OF FLORIDA ADOPTED THE |
| | 2007 FBC WITH THE 2009 SUPPLEMENTS. THE PREVIOUS |
| | FLORIDA BUILDING CODE WAS THE 2004 EDITION. THERE HAS |
| | NOT BEEN A 20096 EDITION. THE PLANS ALSO STATE * THE |
| | LATEST EDITIONS OF OTHER CODES*. PLEASE UNDERSTAND |
| | THERE ARE NUMEROUS CODES WHICH ARE CURRENTLY THE LATEST |
| | EDITIONS HOWEVER THE STATE OF FLORIDA HAS NOT YET |
| | ADOPTED MANY OF THE LATEST EDITIONS. |
| | THE PLANS SHOULD HAVE THE FOLLOWING AT A MINIMUM UNDER |
| | THE DESIGN: |
| | 2007 FBC W/2009 SUPPLEMENTS |
| | 2006 NFPA-101 |
| | 2005 NFPA-70 ( NATIONAL ELECTRICAL CODE) |
| | |
| | PER: FS 553.73, FBC 2007 EDITION WITH 2009 REVISIONS, |
| | FLORIDA ADMINISTRATIVE CODE 69A-3.012, 69A-60.004. |
| | |
| | ** IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | 2) NOTE: THE SUBMITTED ELECTRICAL PLANS DO NOT CONTAIN |
| | ANY DESIGN PROFESSIONAL SIGNED, DATED OR SEALED ON SAID |
| | ELECTRICAL PLANS. PLEASE SEE FS 481.229, 471.003. WHEN |
| | MEETING EXCEPTIONS TO THE REQUIRED DESIGN PROFESSIONAL |
| | AS NOTED THEN PLANS WOULD BE THEN UNDER THE EXCEPTIONS |
| | TO A DESIGN PROFESSIONAL PER FS 489. |
| | ** IF CASTILLO ELECTRIC IS THE DESIGN PROFESSIONAL |
| | PLEASE BE SURE THE PRINTED NAME AND SIGNATURE IS STATED |
| | ON PLANS. |
| | |
| | 3) NOTE: PLEASE SHOW WHERE THE DECLARED LEVEL OF |
| | ALTERATION PER EXISTING BUILDING CODE CHAPTER 4 IS |
| | STATED ON PLANS. THIS IS ALSO A CHANGE IN OCCUPANCY TO |
| | A HIGHER LEVEL OF HAZARD FROM THE PREVIOUS USE. SEE |
| | TABLES IN CHAPTER 8. |
| | |
| | |
| | 4) NOTE: PLEASE COMPLETE ELECTRICAL PLANS WITH ALL |
| | CIRCUITING AND COORDINATE WITH A PANEL SCHEDULE(S) TO |
| | BE SUBMITTED. PLEASE BE SURE TO SEE 700.12F FOR |
| | CIRCUITING OF EMERGENCY AND EXIT LIGHTS TO LOCAL |
| | LIGHTING BRANCH CIRCUIT. SIZE OF CIRCUIT, PANEL, OVER |
| | CURRENT PROTECTION DEVICE ETC NEEDS TO BE SHOWN. |
| | PLEASE ALSO INDICATE LOADS IMPOSED ON EXISTING PANELS |
| | AND THE RATINGS OF EXISTING EQUIPMENT. |
| | |
| | 408.4, 310.16, 240.4, 220.14, 220.12, 220.42, 220.43, |
| | 220.44. THESE ARE ONLY A FEW SECTIONS NOTED. |
| | FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL |
| | INFORMATION NOT YET ON PLANS FOR MINIMUM CODE REVIEW. |
| | |
| | 5) NOTE: PLEASE INDICATE THE NEW OR EXISTING SIGN |
| | CIRCUIT PER 600.5. PLEASE BE SURE TO INCLUDE LOAD. ( |
| | 1200VA MINIMUM) |
| | |
| | 6) NOTE: PLEASE SEE 13-415.AB.1.1, .1.2, .1.3. THIS IS |
| | A TENANT SPACE LOCATED IN BUILDING GREATER THAN 5K SQ |
| | FT. SEE DEFINITIONS OF *BUILDING*, A RATED TENANT |
| | SEPARATION WALL DOES NOT CREATE A SEPARATE BUILDING. |
| | ADJACENT TENANT SPACES ARE ALSO TENANTS LOCATED IN A |
| | BUILDING GREATER THAN 5K SQ FT. |
| | AUTOMATED LIGHTING CONTROLS ARE REQUIRED FOR NEW BEING |
| | INSTALLED. PLEASE ALSO BE AWARE THAT CHANGE IN |
| | OCCUPANCY PER 13-101.3.2 STATES TO COMPLY WITH 13-4 OF |
| | THE FBC. |
| | |
| | 7) NOTE: PLEASE SEE 13-415.AB.1.4 FOR CONTROLS OF |
| | EXTERIOR LIGHTING. THIS MAY BE ONE OF TWO METHODS AS |
| | STATED IN SECTION. |
| | |
| | 8) NOTE: PLEASE SEE FBC 13-415.AB.5, 13-415.B, |
| | 13-415.B.1 AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS |
| | FOR LIGHTING. PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR |
| | LIGHTING. |
| | ** IMPORTANT** LIGHTING FIXTURES WOULD NEED TO BE |
| | SPECIFIC AT THIS TIME. STATING 2FT BY 8FT CEILING |
| | MOUNTED FLUORESCENT IS NOT SPECIFIC. THESE FIXTURE COLD |
| | CONTAIN AS LITTLE AS 4-32W BULBS WITH A MUCH LOWER VA |
| | RATING OR IT COULD BE MUCH HIGHER. |
| | PLEASE SEE SECTIONS NOTED ABOVE AS THE VA/ WATTAGE USED |
| | IN PERFORMANCE CALCULATIONS ARE BASED ON |
| | FIXTURE/BALLAST RATINGS NOT LIGHT BULB WATTAGE. |
| | THE EXTERIOR FIXTURES WHICH ARE ON ARCHITECTURAL PLANS |
| | ARE NOT ON ELECTRICAL PLANS. |
| | |
| | 9) NOTE: PLEASE SEE FBC 1006.1.1, .1.2, NFPA-101 |
| | 7.8.1.3, 7.9.1.2, .2.2. AS REQUIRED EGRESS LIGHTING IS |
| | REQUIRED UNDER NORMAL AND EMERGENCY CONDITIONS. PLEASE |
| | SEE SECTIONS ABOVE SPECIFIC TO STAIR AREAS AT THE REAR |
| | AND SIDE OF THE BUILDING. THE LIGHTING LEVELS REQUIRED |
| | UNDER NORMAL CONDITIONS ARE 10 FC AND IS PERMITTED TO |
| | GO DOWN TO 1FC UNDER EMERGENCY CONDITIONS. PLANS DO NOT |
| | SHOW ANY LIGHTING AT THESE LOCATIONS FOR NORMAL OR |
| | EMERGENCY ILLUMINATION. |
| | SEE POSSIBLE COMMENTS FROM FIRE MARSHAL REVIEW. |
| | |
| | 10) NOTE: ARCHITECTURAL PLANS INDICATE AN ELECTRICAL |
| | PANEL LOCATED IN *OFFICE #1* HOWEVER ELECTRICAL PLANS |
| | DO NOT INDICATE ANY PANEL? |
| | PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT AND |
| | PANELS. |
| | 110.26, 240.24, ETC. |
| | |
| | 11) NOTE: IN LONGUE AREA RECEPTACLE LOCATED AT THE SIDE |
| | OF SINK WOULD HAVE AN OCCUPANT CROSSING OVER THE NEW |
| | SINK TO PLUG IN ANY APPLIANCES LEAVING CORD IN SINK |
| | AREA. THIS IS NOT A SAFE LOCATION FOR RECEPTACLE |
| | SERVING THE COUNTER SPACE AS SHOWN. |
| | PLEASE SEE 210.8B. |
| | PLEASE ALSO INDICATE IF THE EXISTING DEVICES LOCATED IN |
| | BATH ROOMS ARE GFCI PROTECTED. IF THESE ARE NOT PER THE |
| | CHANGE IN OCCUPANCY IN THE EBC, ALL ELECTRICAL SHALL BE |
| | MADE SAFE TO CURRENT CODE REQUIREMENTS. |
| | |
| | ** PLEASE KNOW THAT PLANS ARE NO LONGER RELEASED BACK |
| | TO CONTRACTOR PER NEW DIRECTOR. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |