Plan Review Notes
Plan Review Notes For Permit 09080203
Permit Number 09080203
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-09 09:26:48 
  
 ** DENIED REVIEW **
  
 1) NOTE: PLANS SPECIFICALLY STATE WORK TO BE DONE TO A
 2006 FLORIDA BUILDING AS WELL AS STATING THE 2007
 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS. SEE NOTE
 #4 ON PLANS.
 AS OF MARCH 1ST, 2009 THE STATE OF FLORIDA ADOPTED THE
 2007 FBC WITH THE 2009 SUPPLEMENTS. THE PREVIOUS
 FLORIDA BUILDING CODE WAS THE 2004 EDITION. THERE HAS
 NOT BEEN A 20096 EDITION. THE PLANS ALSO STATE * THE
 LATEST EDITIONS OF OTHER CODES*. PLEASE UNDERSTAND
 THERE ARE NUMEROUS CODES WHICH ARE CURRENTLY THE LATEST
 EDITIONS HOWEVER THE STATE OF FLORIDA HAS NOT YET
 ADOPTED MANY OF THE LATEST EDITIONS.
 THE PLANS SHOULD HAVE THE FOLLOWING AT A MINIMUM UNDER
 THE DESIGN:
 2007 FBC W/2009 SUPPLEMENTS
 2006 NFPA-101
 2005 NFPA-70 ( NATIONAL ELECTRICAL CODE)
  
 PER: FS 553.73, FBC 2007 EDITION WITH 2009 REVISIONS,
 FLORIDA ADMINISTRATIVE CODE 69A-3.012, 69A-60.004.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 2) NOTE: THE SUBMITTED ELECTRICAL PLANS DO NOT CONTAIN
 ANY DESIGN PROFESSIONAL SIGNED, DATED OR SEALED ON SAID
 ELECTRICAL PLANS. PLEASE SEE FS 481.229, 471.003. WHEN
 MEETING EXCEPTIONS TO THE REQUIRED DESIGN PROFESSIONAL
 AS NOTED THEN PLANS WOULD BE THEN UNDER THE EXCEPTIONS
 TO A DESIGN PROFESSIONAL PER FS 489.
 ** IF CASTILLO ELECTRIC IS THE DESIGN PROFESSIONAL
 PLEASE BE SURE THE PRINTED NAME AND SIGNATURE IS STATED
 ON PLANS.
  
 3) NOTE: PLEASE SHOW WHERE THE DECLARED LEVEL OF
 ALTERATION PER EXISTING BUILDING CODE CHAPTER 4 IS
 STATED ON PLANS. THIS IS ALSO A CHANGE IN OCCUPANCY TO
 A HIGHER LEVEL OF HAZARD FROM THE PREVIOUS USE. SEE
 TABLES IN CHAPTER 8.
  
  
 4) NOTE: PLEASE COMPLETE ELECTRICAL PLANS WITH ALL
 CIRCUITING AND COORDINATE WITH A PANEL SCHEDULE(S) TO
 BE SUBMITTED. PLEASE BE SURE TO SEE 700.12F FOR
 CIRCUITING OF EMERGENCY AND EXIT LIGHTS TO LOCAL
 LIGHTING BRANCH CIRCUIT. SIZE OF CIRCUIT, PANEL, OVER
 CURRENT PROTECTION DEVICE ETC NEEDS TO BE SHOWN.
 PLEASE ALSO INDICATE LOADS IMPOSED ON EXISTING PANELS
 AND THE RATINGS OF EXISTING EQUIPMENT.
  
 408.4, 310.16, 240.4, 220.14, 220.12, 220.42, 220.43,
 220.44. THESE ARE ONLY A FEW SECTIONS NOTED.
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION NOT YET ON PLANS FOR MINIMUM CODE REVIEW.
  
 5) NOTE: PLEASE INDICATE THE NEW OR EXISTING SIGN
 CIRCUIT PER 600.5. PLEASE BE SURE TO INCLUDE LOAD. (
 1200VA MINIMUM)
  
 6) NOTE: PLEASE SEE 13-415.AB.1.1, .1.2, .1.3. THIS IS
 A TENANT SPACE LOCATED IN BUILDING GREATER THAN 5K SQ
 FT. SEE DEFINITIONS OF *BUILDING*, A RATED TENANT
 SEPARATION WALL DOES NOT CREATE A SEPARATE BUILDING.
 ADJACENT TENANT SPACES ARE ALSO TENANTS LOCATED IN A
 BUILDING GREATER THAN 5K SQ FT.
 AUTOMATED LIGHTING CONTROLS ARE REQUIRED FOR NEW BEING
 INSTALLED. PLEASE ALSO BE AWARE THAT CHANGE IN
 OCCUPANCY PER 13-101.3.2 STATES TO COMPLY WITH 13-4 OF
 THE FBC.
  
 7) NOTE: PLEASE SEE 13-415.AB.1.4 FOR CONTROLS OF
 EXTERIOR LIGHTING. THIS MAY BE ONE OF TWO METHODS AS
 STATED IN SECTION.
  
 8) NOTE: PLEASE SEE FBC 13-415.AB.5, 13-415.B,
 13-415.B.1 AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS
 FOR LIGHTING. PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR
 LIGHTING.
 ** IMPORTANT** LIGHTING FIXTURES WOULD NEED TO BE
 SPECIFIC AT THIS TIME. STATING 2FT BY 8FT CEILING
 MOUNTED FLUORESCENT IS NOT SPECIFIC. THESE FIXTURE COLD
 CONTAIN AS LITTLE AS 4-32W BULBS WITH A MUCH LOWER VA
 RATING OR IT COULD BE MUCH HIGHER.
 PLEASE SEE SECTIONS NOTED ABOVE AS THE VA/ WATTAGE USED
 IN PERFORMANCE CALCULATIONS ARE BASED ON
 FIXTURE/BALLAST RATINGS NOT LIGHT BULB WATTAGE.
 THE EXTERIOR FIXTURES WHICH ARE ON ARCHITECTURAL PLANS
 ARE NOT ON ELECTRICAL PLANS.
  
 9) NOTE: PLEASE SEE FBC 1006.1.1, .1.2, NFPA-101
 7.8.1.3, 7.9.1.2, .2.2. AS REQUIRED EGRESS LIGHTING IS
 REQUIRED UNDER NORMAL AND EMERGENCY CONDITIONS. PLEASE
 SEE SECTIONS ABOVE SPECIFIC TO STAIR AREAS AT THE REAR
 AND SIDE OF THE BUILDING. THE LIGHTING LEVELS REQUIRED
 UNDER NORMAL CONDITIONS ARE 10 FC AND IS PERMITTED TO
 GO DOWN TO 1FC UNDER EMERGENCY CONDITIONS. PLANS DO NOT
 SHOW ANY LIGHTING AT THESE LOCATIONS FOR NORMAL OR
 EMERGENCY ILLUMINATION.
 SEE POSSIBLE COMMENTS FROM FIRE MARSHAL REVIEW.
  
 10) NOTE: ARCHITECTURAL PLANS INDICATE AN ELECTRICAL
 PANEL LOCATED IN *OFFICE #1* HOWEVER ELECTRICAL PLANS
 DO NOT INDICATE ANY PANEL?
 PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT AND
 PANELS.
 110.26, 240.24, ETC.
  
 11) NOTE: IN LONGUE AREA RECEPTACLE LOCATED AT THE SIDE
 OF SINK WOULD HAVE AN OCCUPANT CROSSING OVER THE NEW
 SINK TO PLUG IN ANY APPLIANCES LEAVING CORD IN SINK
 AREA. THIS IS NOT A SAFE LOCATION FOR RECEPTACLE
 SERVING THE COUNTER SPACE AS SHOWN.
 PLEASE SEE 210.8B.
 PLEASE ALSO INDICATE IF THE EXISTING DEVICES LOCATED IN
 BATH ROOMS ARE GFCI PROTECTED. IF THESE ARE NOT PER THE
 CHANGE IN OCCUPANCY IN THE EBC, ALL ELECTRICAL SHALL BE
 MADE SAFE TO CURRENT CODE REQUIREMENTS.
  
 ** PLEASE KNOW THAT PLANS ARE NO LONGER RELEASED BACK
 TO CONTRACTOR PER NEW DIRECTOR.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  