 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE
 EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF
 ON-SITE OPTIONAL STANDBY POWER SOURCES.
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH AND
 GENERATOR INTENDED TO BE INSTALLED, THE FAXED COPIES
 ARE GENERIC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  