| Plan Review Notes For Permit 09080201 |
| Permit Number |
09080201 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-24 14:59:07 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE | | | EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF | | | ON-SITE OPTIONAL STANDBY POWER SOURCES. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO | | | BE SERVED. 215.5. 702.5, 2005NEC | | | | | | 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH AND | | | GENERATOR INTENDED TO BE INSTALLED, THE FAXED COPIES | | | ARE GENERIC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|