| Plan Review Notes For Permit 09080177 |
| Permit Number |
09080177 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-10 09:51:22 | RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | 2- WITHDRAWAL TESTING REPORT SUBMITTED DOESN'T COMPLY | | | WITH THE REQUIREMENTS OF TAS 105. MINIMUM NUMBER OF | | | TESTS NEED TO COMPLY WITH SEC. 8 OF TAS 105-98. THERE | | | WERE ONLY 6 TESTS PERFORMED. MINIMUM NUMBER OF TESTS | | | NEED TO COMPLY WITH SEC. 8 OF TAS 105. | | | | | | 3- CLARIFY WHY ARE THERE TWO DIFFERENT ENGINEERS, TWO | | | DIFFERENT RAS 117 CALCULATIONS AND TWO DIFFERENT | | | PRODUCT APPROVALS SUBMITTED. | | | | | | 4- ENGINEER (R.N. SAILAPPAN) IS REFERRING TO NOA | | | 07-0228.07 AND APPROVED ASSEMBLY ON SHEET 23 OF 28. | | | THIS NOA WAS NOT SUBMITTED. CLARIFY WHICH PRODUCT | | | APPROVAL AND APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED. | | | | | | 5- CLARIFY WHY ARE THERE TWO DIFFERENT PRODUCT APPROVAL | | | SUBMITTED. ONE IS FOR CONCRETE DECKS AND THE OTHER ONE | | | IS FOR LIGHTWEIGHT CONCRETE DECKS. PLEASE COORDINATE | | | ALL PRODUCT APPROVALS AND RAS 117 CALCULATIONS. | | | NOTE: ASSEMBLY ON SHEET 7 OF NOA 06-0626.03 IS GOOD FOR | | | A MAXIMUM DESIGN PRESSURE OF -305PSF. USING THIS | | | ASSEMBLY DOESN'T REQUIRE ADDITIONAL RAS 117 | | | CALCULATIONS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|