| Plan Review Notes For Permit 09080161 |
| Permit Number |
09080161 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-10-08 09:58:47 | | | | ** TEMPORARY FAILED** | | | | | | ** WAITING FOR THE FOLLOWING INFORMATION. | | | | | | 1) NOTE: CALL WAS PLACED TO PUBLIX CORPORATE OFFICE TO | | | OBTAIN COPY OF CONTRACT FOR SCOPE OF WORK TO VERIFY | | | VALUE. | | | FBC 108.3 | | | | | | 2) NOTE: NEW REVISED ELECTRICAL/GENERATOR SITE PLANS | | | WERE SUBMITTED. THE ENGINEER AS SIGNED AND SEALED ON | | | SHEETS IS NOT THE ENGINEER AS LISTED ON TITLE BLOCKS AS | | | THE RESPONSIBLE DESIGNER OF RECORD. A CALL WAS PLACED | | | TO THE ENGINEER'S PHONE NUMBER AS LISTED ON TITLE BLOCK | | | HOWEVER THIS NUMBER IS NO LONGER THE NUMBER OF THE | | | ENGINEER OF RECORD. | | | FS 471.025, FAC 61G15-23.002 | | | | | | | | | | | | | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|